Siemens SINAMICS G120 Function Manual page 96

Hide thumbs Also See for SINAMICS G120:
Table of Contents

Advertisement

Commissioning
5.6 Setting basic functions
Figure 5-2
An adjustable signal filter in the inverter suppresses temporary signal changes using bit
pattern test or contact bounce.
The filter increases the inverter response time. The inverter only selects its safety function
after the debounce time has elapsed.
Figure 5-3
Parameter
p9650
p9651
For SIMATIC ET 200pro FC, the tolerance time is always 0 ms.
1)
96
Inverter response to a bit pattern test
Filter for suppressing temporary signal changes
Description
F-DI switchover discrepancy time (factory setting: 500 ms)
1)
Tolerance time to switch over the safety input for the basic functions.
STO debounce time (factory setting: 1 ms)
Debounce time of the safety input for the basic functions.
Safety Integrated - SINAMICS G110M, G120, G120C, G120D and SIMATIC ET 200pro FC-2
Function Manual, 04/2014, FW V4.7, A5E34261271B AA

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents