Commissioning
5.7 Setting extended functions
Parameter
p1135
p9501.00
p9506
p9531[0...3]
p9533
p9551
p9563[0...3]
p9581
p9582
p9583
r9722.04
p1135
140
Description
OFF3 ramp-down time
1 signal: Enable SLS and extended functions.
0 signal: Inhibit SLS and extended functions.
Function specification: (Factory setting: 1)
1:
With braking ramp monitoring
3:
Without braking ramp monitoring
Speed monitoring (Factory setting for all levels: 2000 rpm)
Setpoint speed limiting (Factory setting: 80 %)
The inverter limits the setpoint to the value r9733.
r9733[0] = p9531[x] × p9533.
Delay time SLS selection → SLS active (Factory setting: 100 ms)
Not active for braking ramp monitoring.
SLS-specific stop response (Factory setting: STOP A)
0:
STOP A
1:
STOP B
Reference speed (Factory setting: 1500 rpm)
Delay time (Factory setting: 250 ms)
Monitoring time (Factory setting: 10 s)
The gradient of the braking ramp depends on p9581 and p9583.
1 signal: SLS active
0 signal: SLS not active
OFF3 ramp-down time
Safety Integrated - SINAMICS G110M, G120, G120C, G120D and SIMATIC ET 200pro FC-2
Function Manual, 04/2014, FW V4.7, A5E34261271B AA