Commissioning
5.7 Setting extended functions
5.7.5.2
Setting SS1 with acceleration monitoring
Procedure
To set the SS1 function with acceleration monitoring, proceed as follows:
1. Select "[3] Safety without encoder with accel_monitoring (SAM)/delay time".
2. Press the "Safe stop functions" button.
3. Set the following:
–
–
–
–
4. Close the screen form.
You have set the SS1 function with acceleration monitoring.
134
③
Delay time
After this time the inverter safely switches off the motor torque – regardless of the
actual speed.
④
shutdown speed SS1
⑤
speed tolerance
⑥
shutdown speed acceleration monitoring
Safety Integrated - SINAMICS G110M, G120, G120C, G120D and SIMATIC ET 200pro FC-2
Function Manual, 04/2014, FW V4.7, A5E34261271B AA