Operation
6.13 List of alarms and faults
Signal
Cause
Complete information on the messages is available in the List Manual.
A01620,
Safe torque off active
F01620
A01621,
Safe Stop 1 active
F01621
F01625
Sign-of-life error in the Safety data
F01630
Brake control defective
Fault value r0949 provides more
detailed information.
A01631
Motor holding brake / SBC
configuration does not make sense
F01640,
It has been identified that a
F01641
component has been replaced,
acknowledgment/data save is
necessary
F01649
Internal software error
F01650
Acceptance test required
F01651
Synchronization, safety time slices
unsuccessful.
F01653
PROFIBUS configuration error
244
Remedy
6165: Fault in reception of the PROFIsafe telegram. This fault can
also arise if the inverter has received an inconsistent or out-of-date
PROFIsafe telegram after a power on reset or after the
PROFIBUS/PROFINET line has been connected.
Check the configuration and communication in the inverter.
Check the value of the F_WD_Time F-parameter in the inverter.
Increase the value.
6166: Time monitoring fault in reception of the PROFIsafe telegram.
Check the configuration of the communication in the inverter.
Check the setting of the F_WD_Time value in the inverter.
Increase the value.
Evaluate the diagnostic information in the F host.
Check the PROFIsafe connection.
Not necessary.
Not necessary.
1. Select STO, and then deselect again.
2. If it cannot be acknowledged, replace the Control Unit.
Depending on the fault value, check the following:
10, 11: p1278 ≠ 0, brake not connected, cable interrupted or ground
fault
20: Short-circuit in the brake winding
30, 31, 40: Brake not connected or a short-circuit in the brake
winding
50: Fault in the Safe Brake Relay, in the Control Unit or in the Power
Module.
Check and correct the parameterization of the motor holding brake:
The following settings can result in this message:
p1215 = 0 and p9602 = 1.
p1215 = 3 and p9602 = 1.
See Section Corrective maintenance (Page 251).
1. Switch off the Control Unit power supply and then on again.
2. If it cannot be acknowledged, replace the Control Unit.
See Section Acceptance tests for the safety functions (Page 156).
1. Switch off the Control Unit power supply and then on again.
2. If it cannot be acknowledged, replace the Control Unit.
Check the PROFIBUS configuration of the safety slot on the master
side and on the Control Unit.
Safety Integrated - SINAMICS G110M, G120, G120C, G120D and SIMATIC ET 200pro FC-2
Function Manual, 04/2014, FW V4.7, A5E34261271B AA