Operation
6.8 Safe Direction (SDI)
Switching the motor on after an internal event
Procedure
To switch the motor on after an internal event while SDI is active, proceed as follows:
1. Deselect the SDI function.
2. Issue an OFF1 command (ON/OFF1 = 0).
3. Acknowledge the internal event in one of the following ways:
– Fail-safe acknowledgment using PROFIsafe control word 0, bit 7 = 0 → 1 → 0
– Fail-safe acknowledge signal via a safety input: F-DI = 0 → 1 → 0.
– Select the STO function and deselect again (PROFIsafe control word 0, bit 0 or F-DI).
– Select the SS1 function and deselect again (PROFIsafe control word 0, bit 1 or F-DI).
– Switch off the inverter supply voltage and on again (power on reset).
4. Acknowledge the inverter with the "standard" acknowledge signal.
5. Switch on the motor (ON/OFF1 = 1).
You have acknowledged the internal event and switched on the motor again.