Commissioning
5.7 Setting extended functions
Setting PROFIsafe telegram 900
Precondition
You have selected the extended functions "via PROFIsafe" or "via PROFIsafe and onboard
terminals"
Procedure
To set the PROFIsafe telegram 900, proceed as follows:
1. Press the "Safety inputs" button.
2. Enable telegram 900.
If you disable this function, the inverter operates with telegram 30.
3. Set which F-DI status of the inverter is transferred via PROFIsafe status word 5 .
Note
The status of the safety inputs is transferred irrespective of whether you use one of the
safety inputs to control a fail-safe function.
4. Close the screen form.
You have set PROFIsafe telegram 900 in the inverter.
See also Section: Control word 5 and status word 5 (Page 50).
Parameter
p9501.30
p10050
128
Description
Enable F-DI in PROFIsafe telegram(Factory setting: 0 bin)
0 signal: F-DI is inhibited in the PROFIsafe telegram
1 signal: F-DI is enabled in PROFIsafe telegram
Transfer PROFIsafe F-DI (Factory setting: 0000 bin)
Bit 0
0 signal: No transfer
1 signal: PROFIsafe status word 5 transfers the status of F-DI 0
Bit 1
0 signal: No transfer
1 signal: PROFIsafe status word 5 transfers the status of F-DI 1
Bit 2
0 signal: No transfer
1 signal: PROFIsafe status word 5 transfers the status of F-DI 2
Safety Integrated - SINAMICS G110M, G120, G120C, G120D and SIMATIC ET 200pro FC-2