5.6.5

Setting the delay time for SS1

Procedure
Set the delay time for SS1. The delay time must be longer
than the OFF3 ramp-down time.
You have set the SS1 function.
Parameter
p9652
p1135
Description: the SS1 function without monitoring the speed
Figure 5-5
When SS1 is selected, the inverter brakes the motor with the OFF3 ramp-down time.
After the delay time, independent of the actual speed, the inverter switches off the motor
torque using the STO function.
Safety Integrated - SINAMICS G110M, G120, G120C, G120D and SIMATIC ET 200pro FC-2
Function Manual, 04/2014, FW V4.7, A5E34261271B AA
Description
Safe Stop 1 delay time
Sets the delay time of the pulse suppression for the "Safe Stop 1" (SS1) function to
brake with the OFF3 ramp-down time.
OFF3 ramp-down time
SS1 without monitoring the speed
Commissioning
5.6 Setting basic functions
99