Special installation (Horizontal connections)

3.4.12 Horizontal connections

While the display is designed to accommodate side-by-side installations, keep in mind that specific installation
configurations may affect ventilation. Observe the following requirements:
1 Installation of up to three units (Horizontal connection)
The following table lists the operating temperature conditions. Use the units under conditions that keep the
outside atmosphere in this range.
Fan
Fan
Lateral direction
(Total air flow rate:
3
6 m
/min)
Clearance A between
the wall and a unit
A ≥ 300mm
100 ≤ A < 300
20 ≤ A < 100
A < 20
When the unit must be used at temperatures higher than the above, use forced air-cooling until the temperature onthe
intake side and exhaust side of Units A and B is within the specified range.
Outside atmosphere
+5 °C; however, maxi-
mum temperature is
40 °C
50
<Ver. 2.1>
Unit A
Direct each fan either laterally or
downward.
Operating temperature
conditions
0 to 35 °C
0 to 30 °C
Forced air-cooling is
needed.
Cannnot be used.
Unit B
Unit C
If the unit must be used with a clearance of 100 mm or less,
ventilate from under the unit with a fan to forcibly send air in the
direction of the air flow. Use forced air-cooling until the intake
and exhaust temperature values are within the specified range.
A
Downward direction
(Total air flow rate:
3
6m
/min)
Remarks
Outside atmosphere
+ 15 °C