Main Control Module Pcb; Lan Connection - Teletek electronics iRIS8 Installation Manual

Addressable fire alarm control panel
Table of Contents

Advertisement

4.8. Main control module PCB

The Main control module is situated on the back side of the front cover – Figure 14. On the Main control module is
factory integrated a control module - uPC Module, for control of the panel functions and operations.
The Main control module PCB is not a periphery device.
Attention: The iRIS8 panel is delivered with factory set jumpers and interface connections on the Main control module
PCB. DO NOT CHANGE the jumper settings and interface connections to avoid faults and malfunctioning of the panel.
1 - CPU Control module integrated to the Main PCB.
2 - Restore Defaults Jumper for resetting the panel with default parameters.
3 - Openings under the Main PCB for PVC text label with description of the LEDs indication.
4 - Connector to the Interface Module (factory connected).
5 - Connector to the Outputs Control module OUT1 (factory connected).
6 - Interface connector for connection to the Outputs Control module OUT2 – see item 4.4.
7 - ±12V - Additional power supply.
8 - Buzzer for sound signalization.
9 - Built-in 3V backup battery for the real-time clock.
10 - Jumper J1 for battery activation. The jumper J1 is factory set and must not be removed.
11 - LAN interface connector.
12 - Micro USB port for software and firmware update.

4.9. LAN connection

The realization of LAN network is possible only for Repeaters TFT model and iRIS8 series addressable fire alarm
panels (up to 64). The LAN connection can be direct panel-to-panel or by means of a HUB via TCP/IP protocol.
To operate in LAN network with other iRIS8 and Repeater TFT panels the installer must set for all panels "LAN" type of
the communication protocol.
iRIS8 - Addressable Fire Alarm Panel – Installation Manual
Figure 36
Figure 37
29