1.7 sound signalization

signal
After pressing the "RESET" button and upon the initial start-up of the
short beeps
panel.
Fire and/ or Fault operating mode. The signal can be stopped by
Continuous
pressing the "SILENCE BUZZER" button, but the LED indication
beep
remains.
After pressing the "ENABLE/DISABLE" button to enable/disable zones/
Interrupted
sounders and the "TEST/SCROLL" button to access "One Man" test
beep
mode of zones. The signal can be stopped by pressing the "SILENCE
BUZZER" button, but the LED indication remains.

2. Installing the MAG2/4 fire panels

• Choose the best location for the panel position, with an ambient temperature between
-5°C and 40°C, away from heating sources, environmental dust and potential water
ingress.
• Remove all packaging and inspect visually the panel for any damage.
• Remove the outer cover. Stow the cover in a safe position.
• Inspect the internal PCB and make sure the internal components are firmly in place.
• Remove the PCB from the metal / plastic box. Stow in a safe location.
• Choose which cable entry points to knock out and carefully remove the knock-outs.
• Drill the wall to suit the back box centre fixing position, plug and insert a fixing screw.
Note: If you are installing MAG 2/4 in plastic box use the template on the back side of
the packaging box to drill the mounting holes on the wall.
• Fix the metal / plastic housing into mounting position and insert fixing screws.
• Tighten all the fixing screws.
• Route the external cables onto the back box, make off connection glands etc., DO NOT
make any connections at this stage. ENTER THE MAINs CABLE THROUGH ITs
OWN CABLE ENTRY POINT AND KEEP MAINs WIRING AWAY FROM sYsTEM AND
OTHER LOW VOLTAGE WIRING.
• Fit the EOL modules from the supplied additional parts one-by-one to every zone
terminal. ATTENTION: Observe the polarity - the red wire to "+" point and the black
wire to "-" point.
• Fit the EOL resistors from the supplied additional parts one-by-one to the sounders
terminal.
• Re-fit the PCB to the metal / plastic box.
• Place the temperature sensor behind or under the accumulator battery.
• Connect the mains supply and earth to the main terminal block. DO NOT switch on the
main electrical supply at this stage.
• Position the battery in an upright position and place the temperature sensor behind it.
• Close the outer cover using the nuts and screws from the spare parts kit:
Fire Control Panel MAG2/4 - User Manual
Description
7

Advertisement

Table of Contents
loading

This manual is also suitable for:

Mag4

Table of Contents