XL-4, XL-4B, and XL-5 LCD Keypad Programming Manual
Bell Delay
113 BELL DL ATxx
YES
Indicates whether this alarm type should use the system bell delay. If YES then the delay
time will be the duration indicated in the System Timing question (067). The type of bell
output is selected in question #121 (Relay 1 Select). The bell delay option will also apply to
the action selected for relay #2 (question #122) if the relay is not used for smoke detector
reset.
Alarm Type Dialer Delay
114 DIAL DL ATxx
YES
Indicates whether this alarm type should wait for the dialer delay time before
communicating with the Central Station. The dialer delay time is defined in question #068. If
NO dialer delay is selected then this alarm type will transmit immediately. Additionally, if
this question contains yes, the transmissions can be aborted.
Alarm Type Buzzer Enable
115 BUZ EN ATxx
YES
Indicates whether the buzzer (keypad sounder) will be active for this alarm type. If the
condition should be silent at the keypad then enter NO. If the system is partitioned then this
question will relate to all of the keypads defined within that partition.
Display Alarm Option
116 DISPLAY ATxx
YES
Specifies whether this alarm type should visually be displayed at the keypads when an alarm
condition exists. This option should be set to NO only if the condition being defined should
not be annunciated at the keypad (example, silent panic).
If the YES option is selected then an alarm will generate a blinking zone ID light on the LED
display or the appropriate English language display on the LCD display. Press the 0 key to
toggle between the available choices.
U L
Except for silent panic or duress, this option shall be "YES" for UL Listed systems.
Alarm Type Bell Cutoff Select
117 TIMEOUT ATxx
__ (1-3)
Indicates which of the three system bell cutoff periods applies to this alarm type. The system
time-outs have been entered as questions 076 - 078 and relate to whichever relays have been
selected in questions 121 and 122 for this alarm type.
Alarm Type Priority
118 PRIOR ATxx
__ (01-16)
8–40