XL-4, XL-4B, and XL-5 LCD Keypad Programming Manual
Alarm Type Description
109 DESCR ATxx
__________
The Alarm Type descriptions are used to provide English language prompts on the face of the
LCD keypad. The descriptions are not transmitted to the Central Station.
Enter the description, up to ten characters, to be associated with this alarm type. If the
system contains a LCD display then this description will appear on the first line of the
display when an alarm condition has activated.
An explanation of how to enter text through the LCD display can be found in section 4 of this
manual.
Examples of alarm type descriptions would include BURGLARY, FIRE, HOLDUP, LOW
TEMP., etc. The alarm type description should apply to the general condition rather than the
specific zone. When an alarm condition exists, the second line of the LCD display will display
the sixteen character zone description which is defined in question #144, or the keypad
emergency zone description defined in question #176.
Alarm Type CS Code
110 CS CODE ATxx
_ ( 0 - F )
Indicates the code transmitted to the Central Station for this Alarm type. The placement of
the code in the transmission depends on the formats selected for CS#1 & CS#2.
The control panel can transmit to two separate Central Stations and these two receivers can
have different formats. NOTE: For all 2-digit reporting formats (3x1 partial or ext., 4x1
partial or ext., 3x2, and 4x2) this represents the first of the 2 digits. The second digit is the
respective zone CS code. In a standard format (3x1 or 4x1) this code is not used. The only
code is the respective zone CS code.
The following examples are provided for the different formats for transmissions of alarm
conditions;
STANDARD
Example:
123 Z
where Z= Zone CS code (question # 145)
The value entered for the Alarm Type CS code will not be used.
EXTENDED
123 A
AAA Z
where: A = Alarm type CS Code (defined in this question) and Z is the CS code contained
This format can contain either three or four digits within the account number.
PARTIAL EXTENDED
For Alarms
123 Z
where: Z = Zone CS code (question #145). The Alarm Type CS code is not used for this
8–38
in the zone definition (question 145).
format.