Mitsubishi Electric Got 1000 Training Manual page 133

Graphic operation terminal
Hide thumbs Also See for Got 1000:
Table of Contents

Advertisement

7)
6.2.2
Project download
8)
9)
(2) Setting Base Screen No.1
2)
Display the download screen of the project, and download all the data to the GOT.
Reset the PLC CPU using the RESET key switch, and then switch to RUN.
7)
Copy and paste the touch switch created in
section 5.5, change the width size, and make
the settings as follows:
[Basic tab]
Device: M31
Operation: Alternate
Switch color (when it is ON): red
[Text/Lamp tab]
Text: Preparation
Copy OFF → ON
Lamp function: Bit, M31
[Operating Condition]
Trigger Type: OFF
Device: M32
8)
Copy and paste the switch created in 7), and
change the settings as follows:
[Basic tab]
Device: M35
[Text/Lamp tab]
Text: Operation/Stop
Copy OFF → ON
Lamp function: Bit, M35
[Operating Condition]
Trigger Type: ON
Device: M31
9)
Copy and paste the Go To Screen Switch
(control screen) of Base Screen No. 2.
1)
Copy the Go To Screen Switch (alarm) of
Base Screen No. 1, and change the settings
as follows:
[Basic tab]
Switching Screen: Fixed screen 3
[Text/Lamp tab]
Text: Operation screen
Copy OFF → ON
6 - 5