2.2 Wiring

2.2.1

Terminal connection diagram

! ! ! ! 3-phase 200V power input
! ! ! ! 3-phase 400V power input
NFB
3-phase AC
power supply
24VDC power output and
external transistor common
Forward rotation start
Reverse rotation start
Multi-speed selection
Contact input common
Control input signals
(No voltage input allowed)
Frequency setting signals (Analog)
3
(Note 1)
2
Frequency
setting
1
potentiometer
Current input(-)
1/2W1kΩ
4 to 20mADC(+)
When using current input as the
frequency setting signal, set "4" in
any of Pr.180 to Pr.183 (input
terminal function selection) and
assign AU (current input selection)
to any of terminal RH, RM, RL, or
MRS, then turn the AU signal on.
Note: 1. If the potentiometer is to be operated often, use a 2W1kΩ potentiometer.
2. 0.1K and 0.2K do not contain a transistor.
3. Terminals SD and SE are isolated.
4. Term inals S D and 5 are co m m on term inals. D o not earth (ground) them to the
ground . Term inals S D and 5 are not isolated. (Those of the 400V class are isolated.)
5. When terminals PC-SD are used as a 24VDC power supply, be careful not
to short these terminals. If they are shorted, the inverter will be damaged.
6. N ot needed w hen the operation panel or param eter unit (FR -PU 04) is used for
calibration. U sed w hen calibration m ust be m ade near the frequency m eter for
such a reason as a rem ote frequency m eter. H ow ever, the frequency m eter
needle m ay not deflect to full-scale if the calibration resistor is connected. In this
case, use this resistor and the operation panel or param eter unit together.
MC
R(L
)
1
S(L
)
2
T(L
)
3
PC
Note 5
STF
STR
High
RH
Middle
RM
Low
RL
Output stop
MRS
Reset
RES
SD
Note 4
10(+5V)
0 to 5VDC
2
0 to 10VDC
5
(Common)
Note 4
4(4 to 20mADC)
PU connector
(RS-485)
Operation panel
(With frequency setting
potentiometer)
INSTALLATION AND WIRING
U
V
W
P1
Jumper
Remove this jumper when
(+)P
using the optional power-factor
PR
improving DC reactor.
(-)N
Brake resistor connection
Note 2
A
B
Alarm
output
C
RUN
Running
FU
Frequency detection
SE
Open collector
Note 3
output common
(e.g. frequency meter)
Selected
FM
Calibration
resistor (Note 6)
SD
Note 3
Earth
(ground)
16
Motor
IM
Earth
(ground)
Open
collector outputs
Meter
+
-
Moving-coil type
1mA full-scale
Main circuit terminal
Control circuit input terminal
Control circuit output terminal