(1) Example:To change the Pr. 79 "operation mode selection" setting
from "2" (external operation mode) to "1" (PU operation mode)
(For details of Pr. 79, refer to page 124.)
Press the
key, to choose the
MODE
parameter setting mode.
Parameter setting mode
PU
MODE
SET
REV
STOP
FWD
RESET
MIN
MODE
To 3.2.6 Operation mode
Current setting
SET
Flicker
Most significant
digit flickers
SET
MAX
Setting change
Press for
1.5s
SET
Setting write
OPERATION/CONTROL
Middle digit flickers
SET
× 7 times
or
× 3 times
0 to 9
When
appears
1) If the RUN indication is lit or flickering,
stop operation by pressing the
key or turning off the forward rotation
(STF) or reverse rotation (STR) signal
connected to the control terminal.
2) You cannot set any value that is outside the
parameter setting range. Write a value within
the setting range.
"1" (PU operation mode) has been set in Pr. 79.
If the value and
appears, you did not press the
for 1.5s when writing the value.
Press the
key once, press the
restart the setting from the beginning.
64
Least significant
digit flickers
× 9 times
or
× 1 time
SET
0 to 9
RUN
STOP
RESET
do not flicker but
key
SET
key, and
SET