Mitsubishi Electric FR-E520 Instruction Manual page 141

Transistorized inverter
Hide thumbs Also See for FR-E520:
Table of Contents

Advertisement

% % % % Parameter details
Parameter
Setting
Number
9
0 to 500A
0, 100
1, 101
3, 103
13, 113
71 (Note)
23, 123
5, 105
15, 115
6, 106
16, 116
83
0 to 1000V
84
50 to 120Hz
0 to 50Ω,
90
9999
96
Note: The electronic thermal relay function characteristics are also selected
simultaneously. By setting any of "100 to 123", the electronic thermal relay
function changes to the thermal characteristic of the constant-torque motor
when the RT signal switches on.
(2) Tuning execution
• For PU operation or combined operation 2, press the
• For external operation or combined operation 1, switch on the run command.
Note: 1. To force tuning to end
• Switch on the MRS or RES signal or press the
• Switch off the tuning start command to make a forced end.
2. During offline auto tuning, only the following I/O signals are valid:
• Input signals
<Valid signals>
MRS, RES, STF, STR
• Output signals
RUN, FM, A, B, C
3. Special caution should be exercised when a sequence has been designed to
open the mechanical brake with the RUN signal.
Set the rated motor current (A).
Thermal characteristics suitable for standard motor
Thermal characteristics suitable for Mitsubishi's constant-
torque motor
Standard motor
Constant-torque motor
Mitsubishi's SF-JR4P standard motor
(1.5kW or less)
Standard motor
Constant-torque motor
Standard motor
Constant-torque motor
Set the rated motor voltage (V).
Set the rated motor frequency (Hz).
Tuning data
(Values measured by offline auto tuning are set automatically.)
0
Offline auto tuning is not performed.
1
Offline auto tuning is performed.
Description
Star
connection
Delta
connection
or
FWD
STOP
RESET
131
PARAMETERS
Select "offline
auto tuning
setting"
Direct input of
motor constants
enabled
key.
REV
key to end.
4

Hide quick links:

Advertisement

Table of Contents