4.2.48 Stop selection (Pr. 250)

Pr. 250 "stop selection"
Used to select the stopping method (deceleration to a stop or coasting) when the start
signal (STF/STR) switches off.
Parameter
Factory
Number
250
(1) Pr. 250 = "9999"
When the start signal switches off, the motor is decelerated to a stop.
Start signal
Output
frequency
(Hz)
(2) Pr. 250 = 0 to 100s (output is shut off after preset time)
The output is shut off when the time set in Pr. 250 has elapsed after the start signal
was switched off. The motor coasts to a stop.
Start signal
Output
frequency
(Hz)
RUN signal
Setting Range
Setting
0 to 100 s, 1000 to
9999
1100 s, 8888, 9999
ON
Decelerated when start signal switches off.
Related parameters
Pr. 7 "acceleration time"
Pr. 8 "deceleration time"
Pr. 44 "second acceleration/
deceleration time"
Pr. 45 "second deceleration
time"
OFF
Deceleration time (time set in Pr. 8, etc.)
DC brake
OFF
Output is shut off when time set in Pr. 250
has elapsed after start signal was switched
off.
Motor coasts to a stop.
Time