Frequency Jump (Pr. 31 To Pr. 36) - Mitsubishi Electric FR-E520 Instruction Manual

Transistorized inverter
Hide thumbs Also See for FR-E520:
Table of Contents

Advertisement

4.2.14 Frequency jump (Pr. 31 to Pr. 36)

Pr. 31 "frequency jump 1A"
Pr. 32 "frequency jump 1B"
Pr. 33 "frequency jump 2A"
Pr. 34 "frequency jump 2B"
Pr. 35 "frequency jump 3A"
Pr. 36 "frequency jump 3B"
• When it is desired to avoid resonance attributable to the natural frequency of a
mechanical system, these parameters allow resonant frequencies to be jumped. Up
to three areas may be set, with the jump frequencies set to either the top or bottom
point of each area.
• The value set to 1A, 2A or 3A is a jump point and operation is performed at this
frequency.
Parameter
Factory
Number
Setting
31
9999
32
9999
33
9999
34
9999
35
9999
36
9999
<Setting>
• To fix the frequency at 30Hz between Pr. 33 and Pr.
34 (30Hz and 35Hz), set 35Hz in Pr. 34 and 30Hz in
Pr. 33.
• To jump to 35Hz between 30 and 35Hz, set 35Hz in
Pr. 33 and 30Hz in Pr. 34.
Note: During acceleration/deceleration, the running frequency within the set area is
valid.
Setting Range
0 to 400Hz, 9999
0 to 400Hz, 9999
0 to 400Hz, 9999
0 to 400Hz, 9999
0 to 400Hz, 9999
0 to 400Hz, 9999
Frequency jump
Pr.36
Pr.35
Pr.34
Pr.33
Pr.32
Pr.31
101
PARAMETERS
Remarks
9999: Function invalid
9999: Function invalid
9999: Function invalid
9999: Function invalid
9999: Function invalid
9999: Function invalid
Pr.34:35Hz
Pr.33:30Hz
Pr.33:35Hz
Pr.34:30Hz