Procedure For Boot Operation - Mitsubishi 00JCPU User Manual

Q series programmable controller
Table of Contents

Advertisement

11.2.5 Procedure for Boot Operation

This section describes a procedure for boot operation.
In the following procedure,
Section 11.2.3 or Section 11.2.4)
If the RUN/STOP switch is in RUN,
Set the file names of parameters,
programs, initial device values, and device
comments read from the standard ROM
or memory card in the Boot file tab
of the PLC parameter dialog box.
Set the names and execution conditions of
programs to be executed in the Program tab
of the PLC parameter dialog box (This setting
is necessary when one program is written).
Set the parameter-valid drive
with the DIP switches (SW2, SW3).
Select [Online]
in GX Developer and format the memory.
Select [Online] [Write to PLC (Flash ROM)]
[Write to PLC (Flash ROM)] in GX
Developer and write the data to the
memory set in "Transfer from" in the Boot
file tab of the PLC parameter dialog box.
Power off the programmable controller
and then on or reset the CPU module.
NO
CHAPTER11 PROCEDURES FOR WRITING PROGRAM TO CPU MODULE
indicates an operation on the CPU module side.
Start (continued from
set the switch to STOP.
Use the standard
NO
ROM or memory card
(except the Flash card)?
YES
[Format PLC memory]
Is the BOOT LED on?
YES
End
Figure 11.7 Flowchart for boot operation
Section 5.2.8
Section 2.3
GX Developer Version 8 Operating Manual
Section 5.2.6
1
2
11
4
5
6
7
8
11 - 15