(2) PLC system
Parameters required for use of the CPU module are set.
The system can be controlled with default values.
Parameter
Item
No.
Low speed
Timer limit
1000
High
setting
speed
RUN
RUN-
PAUSE
1001
PAUSE
contact
Remote reset
1002
Output mode at STOP to
1003
RUN
Intelligent function
module setting (Interrupt
100A
pointer setting)
Module synchronization
100C
8 - 3
Figure 8.2 PLC system
Table8.2 PLC system setting list
Description
Set the time limit for the low
H
speed timer or high speed timer.
Set the contacts that control
RUN/PAUSE of the CPU module.
Setting of only the PAUSE
H
contact is not allowed. (Setting of
only the RUN contact or the RUN
+ PAUSE contacts is available.)
Select whether to allow the
H
remote reset from GX Developer.
Set the status of the outputs (Y)
when the operating status is
H
switched from STOP to RUN.
Assign the interrupt pointers (I50
to I127) and set the start I/O
H
number and start SI number of
each intelligent function module.
Select whether to synchronize
CPU module startup with
H
intelligent function module
startup.
Setting range
1ms to 1000ms (in increments of 1ms)
0.1ms to 100.0ms (in increments of
0.1ms)
X0 to X7FF
Selected/deselected
Previous state, Recalculate (output is 1
scan later)
• Start I/O No.
• Start SI No.
• I50 to I127
Selected/deselected
Default
Reference
100ms
Section 9.2.10
10.0ms
Section 9.2.10
Section 6.6.1
Blank
Section 6.6.2
Deselected
Section 6.6.3
Previous state
Section 6.4
Blank
Section 6.23
Deselected
-