1.6.1 Starting with the Rack

1.6.1.1
Rack Recommendation
1.6.1.2
Preparing the Rack
The rack may need to be modified to accommodate the 5600 chassis. The distance
between the vertical supports must be between 65 and 80 cm.
Mellanox Technologies
Due to the space required by up to 648 connector cables Mellanox recommends a rack
that is 120 cm long and 80cm wide. This will allow for proper cable management and
enough ventilation to properly cool the chassis.
Mellanox recommends that you remove both sides of the rack to make the installation
easier.
You will need a fork lift, to move and insert the chassis into the rack.

Figure 1: Distance Between the Vertical Supports

This edge of the shelf
must be as close as
possible to the inside of
the door when closed.