Left-Side, Left-Back, Or Left-Bottom Piping; How To Replace The Drain Plug And Drain Hose - Daikin FTXS09JEVJU Installation Manual

R410a split series room air conditioner
Hide thumbs Also See for FTXS09JEVJU:
Table of Contents

Advertisement

3-2. Left-side, left-back, or left-bottom piping

How to replace the drain plug and drain hose

• Replacing onto the left side
1) Remove the insulation fixing screws on the right
and remove the drain hose.
2) Remove the drain plug on the left side and
attach it to the right side.
3) Insert the drain hose and tighten with included
insulation fixing screw.
* (Forgetting to tighten this may cause water
leakages.)
1) Attach the drain hose to the underside of the refrigerant pipes
with adhesive vinyl tape.
2) Be sure to connect the drain hose to the drain port in place of a
drain plug.
3) Shape the refrigerant pipes along the pipe
path marking on the mounting plate.
4) Pass drain hose and refrigerant pipes
through the wall hole, then set the indoor
unit on mounting plate hooks, using the
markings at the top of indoor unit as a
guide.
5) Pull in the inter-unit wiring.
6) Connect the inter-unit piping.
7) Wrap the refrigerant pipes and drain hose together with insulation tape as
right figure, in case of setting the drain hose through the back of the indoor
unit.
8) While exercising care so that the inter-unit wiring do not catch indoor unit,
press the bottom edge of indoor unit with both hands until it is firmly
caught by the mounting plate hooks. Secure indoor unit to the mounting
plate with indoor unit fixing screws 3/16 × 1/2 inch (M4 × 12mm).
3-3. Wall embedded piping
• Insert the drain hose to this depth so it won't be pulled out of the drain pipe.
■English
Drain hose attachment position
* The drain hose is on the back of the unit.
Left side
Attachment on the left side
Insulation
fixing screw
Drain hose
Remove pipe port cover here for left-bottom piping.
How to set drain plug.
Drain
hose
Caulk this hole
with putty or
caulking material.
Right side
Front side of unit
Attachment on the right side (factory default)
Insulation
fixing screw
Drain hose
Left-bottom piping
Do not apply lubricating
oil (refrigeration oil)
when inserting.
Application of causes
deterioration and drain
leakage of the plug.
Insert a hexagonal wrench 3/16" (4mm).
A Mounting plate
Wrap insulating tape around the
Bind with vinyl
bent portion of refrigerant pipes.
tape.
Overlap at least half the width of
the tape with each turn.
Inter-unit wiring
Drain hose
Bottom frame
H Indoor unit fixing screw
3/16" × 1/2" (M4 × 12mm)
(2 point)
Insert the drain
hose to this depth
so it won't be pulled
out of drain pipe.
1-15/16" (50mm)
or more
Outer wall
Remove pipe
port cover
here for left-
side piping.
Left-side
piping
Left-back
piping
A
Mounting
plate
Refrigerant
pipes
Inner wall
Drain hose
Vinyl chloride
drain pipe
(VP-30)
7

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents