Using Conditions for remote control Thermostat

Applicable
The remote control thermostat is only available in wired remote controls.
Method
Unlike with VRV units, the remote control sensor is standard disabled for sky-air units. The use of the
remote control sensor can be enabled by changing field setting 10(20)-2-02 to 10(20)-2-01.
Conditions
The table below contains the condition in which the remote control thermostat is not used:
Condition
1
2
3
Cooling
The diagram below shows the operation range of the set temperature / air suction temperature
combination in cooling operation:
Example: Assuming the preset temperature above is 24°C, and the suction temperature has
changed from 18°C to 30°C (A --> F):
(This example also assumes there are several other air conditioners, the VRV system is off, and that
temperature changes even when the thermostat sensor is off.)
Body thermostat sensor is used for temperatures from 18°C to 23°C (A --> C).
remote control thermostat sensor is used for temperatures from 23°C to 27°C (C --> E).
Body thermostat sensor is used for temperatures from 27°C to 30°C (E --> F).
Part 2 – Functional Description
The remote control thermostat is not used when...
The remote control thermostat malfunctions.
Group control is used.
The set temperature / air suction temperature combination is out of range. (See
below graph)
35
34
32
30
28
TH1 = Ts
26
A
24
22
20
12
14
16
18
20
Range in which thermostat
sensor in remote control can
be used
TH1 = Ts
1
3
B
C
D
E
F
22
24
26
28
30
Range in which body
thermostat sensor can
be used
Functional concept
TH1 = Ts
1
TH1 = Ts
3
32
34
Differential
2–11
1
2
3
4
5