ESIEN05-04
2.3
Setting the infrared remote control
Introduction
To set the infrared remote control, you have to set the address for:
Setting the address
The address for the receiver of the infrared remote control is factory set to 1. To change this setting,
for the receiver
proceed as follows:
Step
1
2
3
4
5
6
Part 4 – Commissioning and Test Run
The receiver of the infrared remote control
The infrared remote control.
Action
Turn OFF the power.
Remove the sealing pad on the top of the receiver.
Small opening
Set the wireless address switch (SS2) according to the table below. You can find the wire-
less address switch attached on the PCB of the receiver and it is visible through the small
opening on the back of the receiver.
Unit No.
SS2
If you use a wired and a infrared remote control for one indoor unit, proceed as follows:
1. Set the wired remote control to MAIN: On the remote control.
2. Set the infrared remote control to SUB: On the receiver with the MAIN/SUB switch
(SS1).
MAIN/SUB
SS1
Seal off the opening of the address switch and the MAIN/SUB switch with the attached
sealing pad.
Sealing pad
Small opening
Make sure to also change the address on the remote control.
Sealing pad
Receiver
No. 1
No. 2
MAIN
S
M
Receiver
Pre-Test Run Checks
S
M
3
2
1
No. 3
SUB
S
M
S
M
3
2
1
1
3
4
5
4–13