Daikin R-410A Service Manual page 225

Sky-air indoor
Hide thumbs Also See for R-410A:
Table of Contents

Advertisement

ESIEN05-04
Setting
To set the field settings, you have to change:
To change the field settings, proceed as follows:
Step
1
2
3
4
5
6
7
Part 4 – Commissioning and Test Run
"Mode No."
"First code No."
"Second code No.".
Action
Hold down the INSPECTION/TEST button for at least 4 s during normal mode to enter
the "Field setting mode".
Press the TEMPERATURE CONTROL button until the desired "Mode No." appears.
If the indoor unit is under group control, all settings for all the indoor units are set at the
same time. Use the codes 10 to 15 to apply this group control and proceed to the next
step.
If you want to set the indoor units of one group individually or if you want to read out
the last settings, use the codes 20 to 25 which are displayed in brackets. Press the
TIMER SELECTION button to select the "Indoor unit No." for which you want to adjust
the field settings.
Press the upper part of the PROGRAMMING TIME button to select the "First code No.".
Press the lower part of the PROGRAMMING TIME button to select the
"Second code No".
Press the CONFIRMATION button to confirm the changed setting.
Press the INSPECTION/TEST button to return to "Normal mode".
Field Settings
1
3
4
5
4–19