Equipment Does Not Operate - Daikin R-410A Service Manual

Sky-air indoor
Hide thumbs Also See for R-410A:
Table of Contents

Advertisement

Troubleshooting
1.3.1

Equipment does not operate

1
Applicable Model
Error Detection
Method
Error Generating
Condition
Possible Causes
3
3
4
5
3–6
All models of SkyAir series
Fuse blown or disorder of contact in operation circuit
Faulty operation switch or contact point
Faulty high pressure switch
Faulty magnetic switch for fan motor
Activation or fault of overcurrent relay for fan motor
Faulty overcurrent relay for compressor
Faulty compressor protection thermostat
Insufficient insulation in electric system
Faulty contact point of magnetic switch for compressor
Malfunction of compressor
Defective remote control or low batteries (wireless)
Check if address is set correctly on wireless R.C.