Field Settings
1
Maintenance Mode
Settings
Mode No.
Function
History error
40
codes
3
Thermistor
41
data display
4
43
Forced fan ON
5
Individual
44
setting
Unit No.
45
change
4–30
The table below describes the maintenance mode settings.
Content and operation method
Display malfunction history
The history No. can be changed with the pro-
gramming time button.
Select the display thermistor with the pro-
gramming time button.
Thermistor:
0. Remote control thermistor
1. Suction thermistor
2. Heat exchanger thermistor.
Turns the fan ON for each unit individually.
Sets fan speed and air flow direction for each
unit individually when using group control.
Settings are made using the "air flow direc-
tion adjust" and "fan speed adjust" buttons.
Confirmation by the confirmation button is
required.
Changes unit No.
Set the unit No. after changing with the pro-
gramming time buttons.
Confirmation by the confirmation button is
required.
Example of the remote control display
Past error code
Unit No.
CODE
SETTING
0: Newest
Malfunction
history
2: Oldest
* "00" displayed for 3 and subsequent
Thermistor
Temperature
Unit No.
SETTING
Unit No.
SETTING
Fan
1: Low
speed
3: High
Air flow direction
Unit No.
SETTING
CODE
Field set No
No after change
Unit No.
SETTING
CODE
Part 4 – Commissioning and Test Run
ESIEN05-04