ESIEN05-04
1.11
PMV Control
Applicable units
All inverter R410A sky-air
Outline
When the automatic mode is selected on the remote-controller, the unit will automatically activate the
PMV control.
The PMV index is a calculated average comfort level.
Refer to ISO 7730 for details.
Function
An optimized indoor temperature will be calculated using the following inputs:
In practice, the set point will be moved with 1 or 2 degrees whenever the conditions change. This will
result in a combination of power saving and increased comfort level.
PMV control can be disabled by changing the field settings:
From: 11(21)-4-01 to: 11(21)-4-02
Part 2 – Functional Description
Outdoor air temperature
Indoor air temperature
remote control set temperature
Functional concept
1
2
3
4
5
2–15