Limit The Maximum And Minimum Output Frequency (Pr. 1, Pr. 2) - Mitsubishi Electric FR-A701 Instrucion Manual

Hide thumbs Also See for FR-A701:
Table of Contents

Advertisement

Before operation
4.3.5

Limit the maximum and minimum output frequency (Pr. 1, Pr. 2)

Motor speed can be limitted.
Parameter
Name
Number
1
Maximum frequency
2
Minimum frequency
Changing example
Limit the frequency set by the potentiometer,
etc. to 60Hz maximum.
(Set "60"Hz in Pr. 1 Maximum frequency.)
1.
Screen at powering on
The monitor display appears.
2.
Press
mode.
3.
Press
setting mode.
4.
5.
Press
"
"(initial value) appears.
6.
Turn
value "
7.
Press
REMARKS
· The output frequency is clamped by the Pr. 2 setting even if the set frequency is lower than the Pr. 2 setting (The frequency will
not decrease to the Pr. 2 setting.)
Note that Pr. 15 Jog frequency has higher priority than the minimum frequency.
· When the Pr. 1 setting is changed, frequency higher than the Pr. 1 setting can not be set by
· When performing a high speed operation at 120Hz or more, setting of Pr. 18 High speed maximum frequency is necessary.
(Refer to chapter 4 of
If the Pr. 2 setting is higher than the Pr. 13 Starting frequency value, note that the motor will run at the set frequency
according to the acceleration time setting by merely switching the start signal on, without entry of the command
frequency.
60
Initial Value
120Hz
0Hz
Operation
to choose the PU operation
to choose the parameter
Pr. 1) appears.
to read the currently set value.
to change it to the set
".
to set.
· By turning
, you can read another parameter.
· Press
to show the setting again.
· Press
twice to show the next parameter.
the instruction manual (applied).)
Setting Range
0 to 120Hz
0 to 120Hz
Output frequency
(Hz)
Pr.1
Pr.18
Pr.2
Clamped at the
minimum frequency
PU indication is lit.
Flicker ··· Parameter setting complete!!
CAUTION
Description
Set the upper limit of the output frequency.
Set the lower limit of the output frequency.
Clamped at the
maximum frequency
Frequency setting
0
5, 10V
(4mA)
(20mA)
Display
The parameter
number read
previously appears.
.

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents