Parameter
Name
PU communication
117
station number
PU communication
118
speed
PU communication
119
stop bit length
PU communication
120
parity check
Number of PU
121
communication
retries
PU communication
122
check time interval
PU communication
123
waiting time setting
PU communication
124
CR/LF selection
Communication
EEPROM write
342
selection
PU mode operation
command source
551
selection
Terminal 2 frequency
125
setting gain frequency
Terminal 4 frequency
126
setting gain frequency
Analog input display
241
unit switchover
Terminal 2 frequency
C2
setting bias frequency
(902)
Terminal 2 frequency
C3
(902)
setting bias
Terminal 2 frequency
C4
setting gain
(903)
Terminal 4 frequency
C5
setting bias frequency
(904)
Terminal 4 frequency
C6
(904)
setting bias
Terminal 4 frequency
C7
setting gain
(905)
The parameter number in parentheses is the one for use with the parameter unit (FR-PU04/FR-PU07).
Incre
Initial
Range
ments
Value
Specify the inverter station number.
Set the inverter station numbers when two
1
0
0 to 31
or more inverters are connected to one
personal computer.
Set the communication speed.
The setting value × 100 equals the
48, 96, 192,
1
192
communication speed.
384
For example, the communication speed is
19200bps when the setting value is "192".
0
Stop bit length: 1bit data length: 8bit
1
Stop bit length: 2bit data length: 8bit
1
1
10
Stop bit length: 1bit data length: 7bit
11
Stop bit length: 2bit data length: 7bit
0
Without parity check
1
2
1
With odd parity check
2
With even parity check
Set the permissible number of retries at
occurrence of a data receive error.
0 to 10
If the number of consecutive errors
exceeds the permissible value, the inverter
1
1
will come to trip.
If a communication error occurs, the
9999
inverter will not come to trip.
0
No PU connector communication
Set the communication check time interval.
If a no-communication state persists for
0.1 to 999.8s
0.1s
9999
longer than the permissible time, the
inverter will come to trip.
No communication check
9999
(signal loss detection)
Set the waiting time between data
0 to 150ms
transmission to the inverter and response.
1
9999
9999
Set with communication data.
0
Without CR/LF
1
1
1
With CR
2
With CR/LF
Parameter values written by communication
0
are written to the EEPROM and RAM.
1
0
Parameter values written by
1
communication are written to the RAM.
Select the RS-485 terminals as PU
1
operation mode control source.
1
2
Select the PU connector as PU operation
2
mode control source.
3
For manufacturer setting. Do not set.
Set the frequency of terminal 2 input gain
0.01Hz
60Hz
0 to 400Hz
(maximum).
Set the frequency of terminal 4 input gain
0.01Hz
60Hz
0 to 400Hz
(maximum).
(Valid when Pr. 858 = 0 (initial value))
0
Displayed in %
1
0
1
Displayed in V/mA
Set the frequency on the bias side of
0.01Hz
0Hz
0 to 400Hz
terminal 2 input.
Set the converted % of the bias side
0.1%
0%
0 to 300%
voltage (current) of terminal 2 input.
Set the converted % of the gain side
0.1%
100%
0 to 300%
voltage of terminal 2 input.
Set the frequency on the bias side of
0.01Hz
0Hz
0 to 400Hz
terminal 4 input.
(Valid when Pr. 858 = 0 (initial value))
Set the converted % of the bias side
0.1%
20%
0 to 300%
current (voltage) of terminal 4 input.
(Valid when Pr. 858 = 0 (initial value))
Set the converted % of the gain side
0.1%
100%
0 to 300%
current (voltage) of terminal 4 input.
(Valid when Pr. 858 = 0 (initial value))
Parameter List
Para
meter
copy
Description
Select the unit for
analog input display.
All
Param
param
eter
eter
clear
clear
: enabled
× : disabled
×
×