Speed Varies During Operation; Operation Mode Is Not Changed Properly; Operation Panel (Fr-Du07) Display Is Not Operating; Power Lamp Is Not Lit - Mitsubishi Electric FR-A701 Instrucion Manual

Hide thumbs Also See for FR-A701:
Table of Contents

Advertisement

5.6.11 Speed varies during operation

When advanced magnetic flux vector control, real sensorless vector control, vector control or encoder
feedback control is exercised, the output frequency varies with load fluctuation between 0 and 2Hz. This is
a normal operation and is not a fault.
1) Inspection of load
Check that the load is not varying.
2) Check the input signals
Check that the frequency setting signal is not varying.
Check that the frequency setting signal is not affected by noise. Input filter to the analog input
terminal using Pr. 74 Input filter time constant and Pr. 822 Speed setting filter 1.
Check for a malfunction due to undesirable currents when the transistor output unit is connected.
(Refer to page 24)
3) Others
Check that the settings of Pr. 80 Motor capacity and Pr. 81 Number of motor poles are correct to the
inverter capacity and motor capacity under advanced magnetic flux vector control, real sensorless
vector control or vector control.
Check that the wiring length is not exceeding 30m when advanced magnetic flux vector control, real
sensorless vector control or vector control is exercised. Perform offline auto tuning. (Refer to chapter 4
of
the instruction manual (applied))
Check that the wiring length is not too long for V/F control.
Change the Pr. 19 Base frequency voltage setting (about 3%) under V/F control.

5.6.12 Operation mode is not changed properly

If the operation mode does not change correctly, check the following:
1) Inspection of load
Check that the STF or STR signal is off.
When it is on, the operation mode cannot be changed.
2) Parameter setting
Check the Pr. 79 setting.
When the Pr. 79 Operation mode selection setting is "0" (initial value), the inverter is placed in external
operation mode at input power-on. At this time, press
the parameter unit (FR-PU04/FR-PU07) is used) to switch to PU operation mode.
Check that the operation location by Pr. 550 and Pr. 551 is correct.
(Refer to chapter 4 of

5.6.13 Operation panel (FR-DU07) display is not operating

Check that the operation panel is connected to the inverter securely.

5.6.14 POWER lamp is not lit

Check that wiring is securely performed and installation is correct.

5.6.15 Parameter write cannot be performed

Make sure that operation is not being performed (signal STF or STR is not ON).
Make sure that you are not attempting to set the parameter in external operation mode.
Check Pr. 77 Parameter write selection.
Check Pr. 161 Frequency setting/key lock operation selection.
Check that the operation location by Pr. 550 and Pr. 551 is correct.
(Refer to chapter 4 of
the instruction manual (applied))
the instruction manual (applied))
Check first when you have troubles
on the operation panel (press
when
5
161

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents