400V class
Type FR-A741-
K
Applicable motor capacity (kW)
Rated capacity (kVA)
*2
Rated current (A)
Overload current rating
*5
Voltage
*6
Regenerative braking torque
Rated input
AC voltage/frequency
Permissible AC voltage fluctuation
Permissible frequency fluctuation
Power supply capacity (kVA)
Protective structure
*9
Cooling system
Approx. mass (kg)
*1
The applicable motor capacity indicated is the maximum capacity applicable for use of the Mitsubishi 4-pole standard motor.
*2
The rated output capacity indicated assumes that the output voltage is 440V.
*3
The % value of the overload current rating indicated is the ratio of the overload current to the inverter's rated output current. For repeated duty,
allow time for the inverter and motor to return to or below the temperatures under 100% load.
*4
The maximum output voltage does not exceed the power supply voltage. The maximum output voltage can be changed within the setting range.
However, the pulse voltage value of the inverter output side voltage remains unchanged at about
*5
The power supply capacity varies with the value of the power supply side inverter impedance (including those of the input reactor and cables).
*6
FR-DU07:IP40 (except for the PU connector)
5.5
7.5
11
5.5
7.5
11
*1
9.1
13
17.5
12
17
23
150% 60s, 200% 3s (inverse time characteristics)
12
17
20
*7
25
26
37
15
18.5
22
15
18.5
22
23.6
29
32.8
31
38
44
surrounding air temperature 50°C
Three-phase 380 to 480V
100% continuous 150% 60s
Three-phase 380 to 480V 50Hz/60Hz
323 to 528V 50Hz/60Hz
±
5%
28
34
41
Open type (IP00)
Forced air cooling
40
48
49
that of the power supply.
2
Rating
30
37
45
30
37
45
43.4
54
65
57
71
86
110
52
66
80
100
65
80
83
115
55
55
84
7
175