Parameter List

4.6.2
Parameter list
·
indicates simple mode parameters.
· The abbreviations in the explanations below indicate:
...V/F control
V/F
V/F
V/F
...advanced magnetic flux vector control
Magnetic flux
Magnetic flux
Magnetic flux
...real sensorless vector control
Sensorless
Sensorless
Sensorless
...vector control.
Vector
Vector
Vector
(Parameters without any indication are valid for all control)
· " " indicates enabled and "×" indicates disabled of "parameter copy", "parameter clear", and "all parameter clear".
Parameter
0
Torque boost
Second torque
46
boost
Third torque boost
112
Maximum
1
frequency
2
Minimum frequency
High speed
maximum
18
frequency
3
Base frequency
Base frequency
19
voltage
Second V/F (base
47
frequency)
Third V/F (base
113
frequency)
Multi-speed setting
4
(high speed)
Multi-speed setting
5
(middle speed)
Multi-speed setting
6
(low speed)
Multi-speed setting
24
(4 speed to 7
to
speed)
27
232
Multi-speed setting
to
(8 speed to 15
speed)
239
98
Incre
Initial
Name
ments
Value
0.1%
3/2%
0.1%
9999
0.1%
9999
0.01Hz
120Hz 0 to 120Hz Set the upper limit of the output frequency.
0.01Hz
0Hz
0.01Hz
120Hz 120 to 400Hz
0.01Hz
60Hz
0.1V
9999
0.01Hz
9999
0.01Hz
9999
0.01Hz
60Hz
0.01Hz
30Hz
0.01Hz
10Hz
0.01Hz
9999
0.01Hz
9999
Range
Set the output voltage at 0Hz as %.
* The initial value differs according to the
0 to 30%
*
inverter capacity. (7.5K or less / 11K or
more )
Set the torque boost when the RT signal is
0 to 30%
on.
9999
Without second torque boost
Set the torque boost when the X9 signal is
0 to 30%
on.
9999
Without third torque boost
0 to 120Hz Set the lower limit of the output frequency.
Set when performing the operation at
120Hz or more.
Set the frequency when the motor rated
0 to 400Hz
torque is generated. (50Hz/60Hz)
0 to 1000V
Set the base voltage.
8888
95% of power supply voltage
9999
Same as power supply voltage
Set the base frequency when the RT signal
0 to 400Hz
is on.
9999
Second V/F is invalid
Set the base frequency when the X9 signal
0 to 400Hz
is ON.
9999
Third V/F is invalid
0 to 400Hz Set frequency when the RH signal is on.
Set frequency when the RM signal is on.
0 to 400Hz
0 to 400Hz
Set frequency when the RL signal is on.
0 to 400Hz,
Frequency from 4 speed to 15 speed can
9999
be set according to the combination of the
RH, RM, RL and REX signals.
0 to 400Hz,
9999: not selected
9999
Description
All
Para
Param
param
meter
eter
eter
copy
clear
clear
: enabled
× : disabled