Limit The Maximum And Minimum Output Frequency (Pr. 1, Pr. 2) - Mitsubishi Electric FR-E700 Basic Instruction Manual

Hide thumbs Also See for FR-E700:
Table of Contents

Advertisement

3.3.5

Limit the maximum and minimum output frequency (Pr. 1, Pr. 2)

Motor speed can be limited.
Parameter
Number
1
Maximum frequency
2
Minimum frequency
Changing
Limit the frequency set by the potentiometer, etc. to 60Hz
example
maximum.
Change 60Hz to Pr. 1 Maximum frequency.
Operation
1.
Screen at powering ON
The monitor display appears.
2.
Press
to choose the PU operation mode.
3.
Press
to choose the parameter setting
mode.
4.
Turn
until
5.
Press
to read the currently set value.
"
"(120.0Hz (initial value)) appears.
6.
Turn
to change the set value to
"
" (60.00Hz).
7.
Press
to set.
Turn
Press
Press
REMARKS
If the set frequency is less than Pr. 2, the output frequency is clamped at Pr. 2 (will not fall below Pr. 2). Note that Pr. 15 Jog
frequency has higher priority than the minimum frequency.
When the Pr. 1 setting is changed, frequency higher than the Pr. 1 setting can not be set by
When performing a high speed operation at 120Hz or more, setting of Pr. 18 High speed maximum frequency is necessary.
(
Refer to the chapter 4 of the Instruction Manual (applied)).
Note that when Pr. 2 is set to any value equal to or more than Pr. 13 Starting frequency, simply turning on the start signal
will accelerate the motor to the set frequency of Pr. 2 according to the set acceleration time even if the command
frequency is not input.
Name
Initial Value
120Hz
0Hz
(Pr. 1) appears.
to read another parameter.
to show the setting again.
twice to show the next parameter.
CAUTION
Setting Range
0 to 120Hz
Set the upper limit of the output frequency.
0 to 120Hz
Set the lower limit of the output frequency.
Output frequency (Hz)
Pr. 1
Pr. 18
Pr. 2
0
Clamped at the
(4mA)
minimum frequency
Display
PU indication is lit.
PRM indication is lit.
(The parameter number read previously appears.)
Flicker ··· Parameter setting complete!!
Before operation
Description
Clamped at the
maximum frequency
Frequency setting
5, 10V
(20mA)
.
45