Mitsubishi Electric FR-A701 Instrucion Manual page 129

Hide thumbs Also See for FR-A701:
Table of Contents

Advertisement

Parameter List
Parameter
Life alarm status
255
display
Inrush current limit
256
circuit life display
Control circuit
257
capacitor life
display
Main circuit
258
capacitor life
display
Main circuit
259
capacitor life
measuring
Power failure stop
261
selection
Subtracted
262
frequency at
deceleration start
Subtraction starting
263
frequency
Power-failure
264
deceleration time 1
Power-failure
265
deceleration time 2
Power failure
deceleration time
266
switchover
frequency
UV avoidance
294
voltage gain
267
Refer to Pr. 73.
268
Refer to Pr. 52.
269
Parameter for manufacturer setting. Do not set.
122
Incre
Initial
Name
ments
Value
1
0
1%
100%
1%
100%
1%
100%
1
0
1
0
0.01Hz
3Hz
0.01Hz
60Hz
0.1/
5s
0.01s
0.1/
9999
0.01s
0.01Hz
60Hz
0.1%
100%
Range
Description
Displays whether the control circuit
capacitor, main circuit capacitor, cooling
(0 to 15)
fan, and each parts of the inrush current
limit circuit has reached the life alarm
output level or not. Reading only
Displays the deterioration degree of the
(0 to 100%)
inrush current limit circuit. Reading only
Displays the deterioration degree of the
(0 to 100%)
control circuit capacitor. Reading only
Displays the deterioration degree of the
(0 to 100%)
main circuit capacitor. Reading only
The value measured by Pr. 259 is displayed.
Setting "1" and turning the power supply off
starts the measurement of the main circuit
capacitor life.
0, 1
When the Pr.259 value is "3" after powering
on again, the measuring is completed.
Read the deterioration degree in Pr.258.
Coasting to stop
0
When undervoltage or power failure
occurs, the inverter output is shut off.
Without UV
1
avoidance
11
With UV avoidance
Without UV
2
avoidance
12
With UV avoidance
Normally operation can be performed with
the initial value unchanged. But adjust the
0 to 20Hz
frequency according to the magnitude of
the load specifications (moment of inertia,
torque).
When output frequency ≥ Pr. 263
Decelerate from the speed obtained
0 to 120Hz
from output frequency - Pr. 262.
When output frequency < Pr. 263
Decelerate from output frequency
Decelerate from the speed obtained from
9999
output frequency - Pr. 262.
0 to 3600/
Set a deceleration slope down to the
360s
frequency set in Pr. 266.
0 to 3600/
Set a deceleration slope below the
360s
frequency set in Pr. 266.
9999
Same slope as in Pr. 264
Set the frequency at which the
0 to 400Hz
deceleration slope is switched from the Pr.
264 setting to the Pr. 265 setting.
Adjust response level at UV avoidance
0 to 200%
operation. A larger setting will improve
responsiveness to the bus voltage change.
Para
Param
meter
eter
copy
clear
: enabled
× : disabled
×
×
×
×
×
×
×
×
When undervoltage
or a power failure
occurs, the inverter
can be decelerated
to a stop.
When undervoltage
or a power failure
occurs, the inverter
can be decelerated
to a stop.
If power is restored
during a power
failure, the inverter
accelerates again.
All
param
eter
clear
×
×
×
×

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents