Wiring; Terminal Connection Diagram - Mitsubishi Electric FR-A701 Instrucion Manual

Hide thumbs Also See for FR-A701:
Table of Contents

Advertisement

Terminal connection diagram

2 WIRING

2.1 Terminal connection diagram
Sink logic
Main circuit terminal
Control circuit terminal
Three-phase AC
power supply
*1. To supply power to the
control circuit separately,
remove the jumper across
R1/L11 and S1/L21.
Control input signals (No voltage input allowed)
Terminal functions vary with
the input terminal
assignment (Pr. 178 to Pr. 189)
(Refer to chapter 4 of the instruction
manual (applied))
holding selection
Multi-speed
selection
*2. JOG terminal can be used
as pulse train input terminal.
Use Pr. 291 to select
JOG/pulse.
Second function selection
*3. AU terminal can be
used as PTC input
terminal.
Terminal 4 input selection
(Current input selection)
Selection of automatic restart
after instantaneous
power failure
Contact input common
(Common for external power supply transistor)
Frequency setting signal (Analog)
Frequency setting
potentiometer
1/2W1k Ω
*5
* 4. Terminal input specifications
can be changed by analog
input specifications
Auxiliary
switchover (Pr. 73, Pr. 267).
input
Set the voltage/current input
switch in the OFF position to
Terminal
select voltage input (0 to 5V/0
4 input
to10V) and ON to select
(Current
current input (4 to 20mA).
input)
(Refer to chapter 4 of the
instruction manual (applied))
*5 . It is recommended to use 2W1kΩ
when the frequency setting signal
is changed frequently.
CAUTION
· To prevent a malfunction due to noise, keep the signal cables more than 10cm away from the power cables. Also separate the main circuit wire
of the input side and the output side.
· After wiring, wire offcuts must not be left in the inverter.
Wire offcuts can cause an alarm, failure or malfunction. Always keep the inverter clean.
When drilling mounting holes in an enclosure etc., take care not to allow chips and other foreign matter to enter the inverter.
· Set the voltage/current input switch correctly. Different setting may cause a fault, failure or malfunction.
12
MC
MCCB
R/L1
S/L2
T/L3
R1/L11
Jumper
S1/L21
*1
Earth
(Ground)
Forward
STF
rotation
start
STR
Reverse
rotation
start
STOP
Start self-
High speed
Middle
speed
Low speed
JOG
Jog mode
MRS
Output stop
RES
Reset
24VDC power supply
10E(+10V)
10(+5V)
3
2
2
5
1
(+)
1
(-)
(+)
4
(-)
Connector
for plug-in option
connection
P/+
*6
Main circuit
Control circuit
RH
RM
RL
*2
RT
*3
AU
AU
PTC
CS
SD
PC
PU
connector
*4
Voltage/current
input switch
4 2
ON
USB
OFF
connector
0 to 5VDC
(Initial value)
0 to 10VDC
selected
*9
*4
0 to 20mADC
(Analog common)
0 to ± 10VDC
(Initial value)
selected
0 to ± 5VDC
*4
4 to 20mADC
(Initial value)
0 to 5VDC
*4
selected
0 to 10VDC
Option connector 1
Option connector 2
Option connector 3
Terminating
resistor
N/-
*6
U
V
W
*6. Do not connect any options to P/+ and
N/-.
C1
Terminal functions
B1
Relay output 1
vary with the output
(Fault output)
terminal assignment
A1
(Pr. 195, Pr. 196)
(Refer to chapter 4 of the
instruction manual
C2
(applied))
B2
Relay output 2
A2
Open collector output
RUN
Running
Terminal functions
SU
vary with the output
Up to frequency
terminal assignment
IPF
(Pr. 190 to Pr. 194)
Instantaneous
power failure
(Refer to chapter 4 of the
OL
instruction manual
Overload
(applied))
FU
Frequency detection
SE
Open collector output common
Sink / source common
* 7. It is not necessary when
calibrating the indicator
from the operation panel.
*9 . Because the FR Configurator has not
worked with the FR-A701 series, a USB
connector can not be used.
+
-
FM
*8
Calibration
resistor * 7
SD
AM
(+)
Analog signal output
(0 to 10VDC)
5
(-)
RS-485 terminals
TXD+
Data transmission
TXD-
RXD+
Data reception
RXD-
SG
GND
VCC
(Permissible load
5V
current 100mA)
Motor
IM
Earth (Ground)
Relay output
*8. FM terminal can be
used for pulse train
output of open
collector output
using Pr.291.
Indicator
(Frequency meter, etc.)
Moving-coil type
1mA full-scale