4. Installation
24
4.7.3.
n Open flue (B23, B23P, B33)
If using an open version, the air supply opening remains open; only
the combustion gas opening is connected. The boiler then takes in
the combustion air required directly from the premises in which it is
installed.
Chimney length for the open version
Diameter
T002998-A
100 mm 40 m 40 m 27 m 24 m 19 m
110 mm 40 m 40 m 40 m 40 m 37 m
n Room sealed flue (C13, C33, C43, C63, C93)
If using a room sealed version, both the combustion gas exhaust
opening and the air supply opening must be connected
(concentrically). Refer to the table to determine the maximum pipe
length of the flue gas pipes in room sealed operation.
Chimney length for room sealed operation
L
Diameter
80-125 mm 20 m 16 m
100-150 mm 20 m 20 m 13 m 13 m 7 m
T001882-B

Lengths of the air/flue gas pipes

The boiler is also suitable for longer chimney lengths
4
with diameters other than those indicated in the
table. Please contact us for further information.
To define the maximum final length, you must remove
4
the pipe length in accordance with the reduction table.
CAUTION
The air supply opening must remain open.
4
The premises in which the appliance is installed must
4
be fitted with the necessary air supply openings.
They must not be reduced or closed.
Maximum length (L)
Quinta Pro
30
45
65
80 mm 40 m 33 m 10 m
90 mm 40 m 40 m 18 m 16 m 12 m
Maximum length (L)
Quinta Pro
30
45
Quinta Pro 30 - 45 - 65 - 90 - 115
90
115
9 m
8 m
65
90
115
-
-
-
09/06/2011 - 123157-AF