7.3.4.

Checking combustion

The check on combustion is done by measuring the percentage of
O
/CO
in the flue gas discharge flue. To do this, proceed as follows:
2
2
1. Unscrew the plug of the flue gas measurement point.
2. Connect the flue gas analyser.
CAUTION
Ensure that the opening around the sensor is completely
sealed when taking measurements.
T001581-A
3. Set the boiler to full load. Press the two B keys simultaneously.
The B symbol is visible on the menu bar and h3 appears in the
display. The boiler is now operating at full load.
4. Measure the percentage of CO
checking values given.
¼ See chapter: "Setting the air/gas ratio (Full load)", page
51.
5. Set the boiler to part load. Press the [-] key several times until
l3 is displayed on the screen. The boiler is now operating on
part load.
6. Measure the percentage of CO
checking values given.
¼ See chapter: "Setting the air/gas ratio (Part load)", page
52.
7. Checking and maintenance
and compare this value with the
2
and compare this value with the
2
67