Error Readout Memorised - REMEHA Quinta Pro 30 Installation And Service Manual

Wall-hung gas condensing boilers
Table of Contents

Advertisement

Quinta Pro 30 - 45 - 65 - 90 - 115
4x
2x
09/06/2011 - 123157-AF
8.3.1.

Error readout memorised

1. Press the two keys f simultaneously and then key [+] until the
symbol c flashes on the menu bar.
2. Select the installers menu using the key S . c0de appears
on the display.
3. Use keys [-] or [+] to input the installer code 0012 .
4. Press the S key. er[xx appears on the display.
5. The fault list or shutdown list can be displayed by pressing the
[-] or [+] key..
6. Confirm using key S . er[xx is displayed with xx
flashing = Last error which occured, For example K2 .
7. Use the [-] or [+] key to scroll through the faults or shutdowns.
8. Press the S key to display the details of the faults or shutdowns.
9. Press the [-] or [+] key to view the following information:
M[1 = Number of times that the error occured.
hr = The number of operating hours.
5t = State.
5v = Sub-status.
t1 = Supply temperature (°C).
t" = Return temperature (°C).
t3 = Calorifier temperature (°C).
t4 = Outside temperature (°C) (Only with an outside
temperature sensor).
t5 = Solar boiler temperature (°C).
5p = Internal set point (°C).
fl = Ionization current (µA).
Mf = Fan speed in rpm.
pr = Water pressure (bar).
T001530-B
p; = Supplied relative heat output (%).
10.Press the > key to interrupt the display cycle. er[xx is
displayed with xx flashing = Last error which occured.
11.Use the [-] or [+] key to scroll through the faults or shutdowns.
12.Press the > key to show the fault list or shutdown list.
13.Press > times on the key 2 to exit the error memory.
8. Troubleshooting
79

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents