Checking The Automatic Air Vent; Checking The Siphon - REMEHA Quinta Pro 30 Installation And Service Manual

Wall-hung gas condensing boilers
Table of Contents

Advertisement

7. Checking and maintenance
1
4
5
5
6
68
2
3
Gas/Gaz
90º
4
5
R000076-A
7.3.5.

Checking the automatic air vent

1. Switch off the boiler electrical power supply.
2. Close the gas valve on the boiler.
3. Close the main gas inlet valve.
4. Unscrew the two screws located under the front panel by a quarter
turn and remove the panel.
5. Tilt the control box forwards by opening the holding clips located
at the sides.
6. Check whether there is any water in the small hose on the
automatic air vent.
7. If any leaks are detected, replace the air vent.
7.3.6.

Checking the siphon

1. Remove the siphon and clean it.
2. Fill the siphon with water.
3. Put the siphon back in place.
Quinta Pro 30 - 45 - 65 - 90 - 115
09/06/2011 - 123157-AF