Connection Possibilities For The Pcb (Scu- S02) - REMEHA Quinta Pro 30 Installation And Service Manual

Wall-hung gas condensing boilers
Table of Contents

Advertisement

Quinta Pro 30 - 45 - 65 - 90 - 115
1
2 %
F 4AT
SCU-SO2
X1
X3
Pump
3wV
EgV
N L
N C
D
N L
Pump
3wV
EgV
N
L
N C D
N L
09/06/2011 - 123157-AF
1
1
T000800-A
D3
X2
X4
X5
Status
Nc
C
No
Tsol Gps
Hru
Nc
C
No
Tsol
Gps
Hru
T001255-B
n Analogue heat output-based control (%)
The 0-10V signal controls the boiler output between 0% and 100%.
The minimum and maximum values are limited. The minimum output
is linked to the boiler's modulation depth. The output varies between
the minimum and maximum value on the basis of the value
determined by the controller.
Jumper 2 Input signal (V) Heat output (%) Description
(1)
0 - 2,0
(1)
2,0 - 2,2
%
(1)
2,0 - 10
(1) Dependent on the minimum modulation depth (set speeds, standard 20%)
n Analogue output (0-10 V)
The temperature or heat output can be chosen for this feedback
message. The two controls are described briefly below.
A jumper (1) on the interface is used to select either temperature
control (*) or heat output control (%).
Jumper 1 Output signal (V) Temperature À Description
0,5
*
1 - 10
Jumper 1 Output signal (V) Heat output (%) Description
0
0,5
%
(1)
2,0 - 10
(1) Dependent on the minimum modulation depth (set speeds, standard 20%)
4.9.3.
Connection possibilities for the PCB (SCU-
S02)
If the boiler is fitted with the control PCB (SCU-S02), then this is
automatically recognised by the automatic control unit of the boiler.
CAUTION
On removing this PCB, the boiler will show fault code
e[38. To prevent this fault, an auto-detect must be
carried out after removing this PCB.
¼ See chapter: "Carrying out an auto-detect", page
61.
The status indicator D3 at the top right of the control PCB indicates
the status:
4 Continuous signal: PCB working normally
4 Flashing signal: No connection
4 No signal: No voltage or faulty PCB (Check the wiring)
0 - 20
Boiler off
20 - 22
Hysteresis
20 - 100
Heat output requested
-
Alarm
10 - 100
Delivered temperature
0 - 15
Boiler off
15 - 20
Alarm
20 - 100
Heat output supplied
4. Installation
37