Connect Frost Protection - REMEHA Quinta Pro 30 Installation And Service Manual

Wall-hung gas condensing boilers
Table of Contents

Advertisement

4. Installation
On/off
OT
BL
RL
Tk
Tv
32
4.8.7.
n Frost protection in combination with on/off thermostat
If an on/off thermostat is used, it is advisable to protect any rooms
where there is risk of frost by using a frost thermostat. The radiator
Tout
Tdhw
valve in a room where there is a risk of frost must, however, be open.
4 In rooms where there is a risk of frost, a frost thermostat (Tv)
should preferably be installed.
4 Connect the frost thermostat in parallel with an on/off room
thermostat (Tk) to the On/off-OT terminals of the connector.
T000778-C
n Frost protection in combination with an outside sensor
The central heating system can also be protected against frost in
combination with an outside sensor. The radiator valve in a room
where there is a risk of frost must, however, be open. Connect the
outside sensor to the Tout terminals of the connector.
The frost protection functions as follows where an outside sensor is
used:
4 At an outside temperature lower than -10°C (can be set with
parameter p30): the circulation pump switches on.
4 At an outside temperature higher than -10°C (can be set with
parameter p30): the circulation pump continues to run and then
switches off.

Connect frost protection

When using a OpenTherm thermostat, a frost thermostat
cannot be connected in parallel to the On/off-OT
terminals. Implement frost protection for the central heating
system in combination with an external sensor.
Quinta Pro 30 - 45 - 65 - 90 - 115
09/06/2011 - 123157-AF