Connecting The Outside Temperature Sensor - REMEHA Quinta Pro 30 Installation And Service Manual

Wall-hung gas condensing boilers
Table of Contents

Advertisement

Quinta Pro 30 - 45 - 65 - 90 - 115
On/off
OT
BL
RL
Tout Tdhw
On/off
OT
BL
RL
Tout Tdhw
90
70
50
30
10
-20
-10
0
09/06/2011 - 123157-AF
Tk
T001590-B
Ba
T001591-B
F
10
20
R000038-A
n Connect on/off thermostat
ON/OFF room thermostat
Tk
The boiler is suitable for connection to a 2 wire on/off room thermostat.
4 Install the regulator in the reference room (generally the living
room).
4 Connect the 2 wire 24V room thermostat to the On/off-OT
terminals of the connector.
4 Connect the power stealing thermostat to the On/off-OT terminals
of the connector.
If a room thermostat with an anticipation element is used,
this must be converted using parameter p5.
4.8.6.
Connecting the outside temperature
sensor
Outside sensor
Ba
An outside sensor can be connected to the Tout terminals of the
connector. Where there is an on/off thermostat controller, the boiler
will control the temperature with the set point of the internal heating
curve.
A OpenTherm controller can also use this outside sensor.
The heating curve required must then be set on the
controller.
n Heating curve setting
If an outside temperature sensor is connected, it is possible to adapt
the heating curve. The setting can be modified using parameters
p1, p"5, p"6 and p"7.
4. Installation