Lengths Of The Air/Flue Gas Pipes - REMEHA Gas 120 ACE Series Installation And Service Manual

Floor-standing condensing gas boiler
Hide thumbs Also See for Gas 120 ACE Series:
Table of Contents

Advertisement

Tab.22
Lengths of the air/flue gas pipes in metres
Configura­
Description
tion
B
Single rigid chimney pipes (combus­
23
tion air taken from the premises)
B
23P
B
Single rigid chimney pipes (combus­
23
tion air taken from the premises)
B
23P
B
Single rigid chimney pipes (combus­
23
tion air taken from the premises)
B
23P
B
Single flexible chimney pipes (com­
23
bustion air taken from the premises)
B
23P
B
Single flexible chimney pipes (com­
23
bustion air taken from the premises)
B
23P
C
Concentric rigid pipes connected to
13
a horizontal terminal
C
13X
C
Concentric rigid pipes connected to
13
a horizontal terminal
C
13X
C
Concentric rigid pipes connected to
33
a vertical terminal
C
33X
C
Concentric rigid pipes connected to
33
a vertical terminal
C
33X
C
Bi-flow adapter and separate single
53
rigid air/flue gas pipes (combustion
air taken from outside)
C
Bi-flow adapter and separate single
53
rigid air/flue gas pipes (combustion
air taken from outside)
C
Concentric pipes in the boiler
93
room
C
93X
Single rigid pipes in the chimney
(combustion air in counter-current)
C
Concentric pipes in the boiler
93
room
C
93X
Single rigid pipes in the chimney
(combustion air in counter-current)
C
Concentric pipes in the boiler
93
room
C
93X
Single rigid pipes in the chimney
(combustion air in counter-current)
7717202 - v03 - 24062019
5.7.2

Lengths of the air/flue gas pipes

The maximum lengths (Lmax) given in the table are valid for pipes in
which the horizontal sections do not exceed one metre in total. For each
additional metre of horizontal pipe, a multiplication coefficient of 1.2 must
be applied when calculating the total length L. The total length L is
calculated by adding the lengths of the straight air/flue gas pipes and the
equivalent lengths of the other components.
Always ensure that L is less than Lmax.
Important
For the list of flue gas system accessories and the equivalent
lengths, refer to the current price list.
Materials
Diameter
PPS
80 mm
PPS
100 mm
PPS
110 mm
PPS
80 mm
PPS
110 mm
PPS/Aluminium
80/125 mm
PPS/Aluminium
100/150 mm
PPS/Aluminium
80/125 mm
PPS/Aluminium
100/150 mm
PPS/Aluminium
80/125 mm over
2x80 mm
PPS/Aluminium
100/150 mm over
2x100 mm
PPS/Aluminium
80/125 mm
80 mm
PPS/Aluminium
80/125 mm
110 mm
PPS/Aluminium
110/150 mm
110 mm
5 Installation
Gas 120
Gas 120
Gas 120
ACE - 65
ACE - 90
ACE - 115
-
-
-
26
24
19
40
40
40
-
-
-
29.5
24
17.5
-
-
-
9
8
5.9
-
-
-
11.5
10
9.4
-
-
-
23
17.5
Air: 11
Flue
gases: 5
-
-
-
-
-
-
16
13.2
10
Gas 120 ACE
33

Hide quick links:

Advertisement

Table of Contents
loading

This manual is also suitable for:

Gas 120 ace - 65Gas 120 ace - 90Gas 120 ace - 115

Table of Contents