Error Memory - REMEHA Quinta Pro 30 Installation And Service Manual

Wall-hung gas condensing boilers
Table of Contents

Advertisement

8. Troubleshooting
Shutdown
Description
code
Configuration procedure
(1)
5v[20
active
Communication error with the
5v[21
SU PCB
No flame during operation
5v[22
Internal error on the SU PCB
5v[25
(1) These lock-outs are not stored in the fault memory
8.3

Error memory

78
Probable causes
Active for a short time
4
after switching on the
boiler
Bad connection
4
No ionization current
4
The boiler control is equipped with an error memory. The last 16 errors
encountered are recorded in this memory.
In addition to the error codes, the following data are also saved:
4 Number of times that the error occured: (MK[xx).
4 Boiler operating mode selected (5t[xx).
4 The flow temperature (t1[xx) and the return temperature
(t2[xx) when the error occured.
To view the error memory, you first have to enter access code
0012.
Quinta Pro 30 - 45 - 65 - 90 - 115
Checking / solution
No action required
4
Check whether the PCU PCB has been
4
correctly fitted in the connector on SU PCB
Purge the gas supply to remove air
4
Check that the gas valve is fully opened
4
Check the supply pressure
4
Check the operation and setting of the gas
4
valve unit
Check that the air inlet and flue gas discharge
4
flues are not blocked
Check that there is no recirculation of flue
4
gases
Replace the SU PCB
4
09/06/2011 - 123157-AF