Powerware series rack-mount ups 500–1500 va
Hide thumbs Also See for 5115:

Advertisement

Powerware Series
®
Eaton 5115 Rack-Mount UPS
500–1500 VA
User's Guide

Advertisement

Table of Contents
loading
Need help?

Need help?

Do you have a question about the 5115 and is the answer not in the manual?

Questions and answers

Summary of Contents for Eaton 5115

  • Page 1 Powerware Series ® Eaton 5115 Rack-Mount UPS 500–1500 VA User's Guide...
  • Page 2 National Electrical Code and NEC are registered trademarks of National Fire Protection Association, Inc. All other trademarks are property of their respective companies. ECopyright 2002–2010 Eaton Corporation, Raleigh, NC, USA. All rights reserved. No part of this document may be reproduced in any way without the express written approval of Eaton Corporation.
  • Page 3 Class B EMC Statements FCC Part 15 This equipment has been tested and found to comply with the limits for a Class B digital device, pursuant to NOTE part 15 of the FCC Rules. These limits are designed to provide reasonable protection against harmful interference in a residential installation.
  • Page 4: Special Symbols

    Special Symbols The following are examples of symbols used on the UPS or accessories to alert you to important information: CAUTION Risk of Electric Shock Do Not Open Cover CAUTION To reduce the risk of electric shock, Do not remove cover (or back) No user-serviceable parts inside Refer servicing to the factory RISK OF ELECTRIC SHOCK - Observe the warning associated with the risk of electric...
  • Page 5: Table Of Contents

    ..............164201449 Rev B www.eaton.com/powerquality Eaton 5115 Rack-Mount UPS (500–1500 VA) User's Guide...
  • Page 6 ..........164201449 Rev B www.eaton.com/powerquality Eaton 5115 Rack-Mount UPS (500–1500 VA) User's Guide...
  • Page 7: Introduction

    The slim design and wide range of installation possibilities make the Eaton 5115 RM the most versatile UPS available. With only 1U (1.75”) of rack-height, the UPS can be installed in rack-mount, wall-mount, side-mount (zero-U), and bench-top applications.
  • Page 8 Advanced power management with the Software Suite CD for graceful shutdowns and power monitoring. Sequential shutdown and load management through separate receptacle groups, called load segments. Backed by worldwide agency approvals. 164201449 Rev B www.eaton.com/powerquality Eaton 5115 Rack-Mount UPS (500–1500 VA) User's Guide...
  • Page 9: Safety Warnings

    To comply with international standards and wiring regulations, the total equipment connected to the output of this UPS must not have an earth leakage current greater than 3.5 milliamperes. 164201449 Rev B www.eaton.com/powerquality Eaton 5115 Rack-Mount UPS (500–1500 VA) User's Guide...
  • Page 10 UPS-ledningsføringen). Netledningen må ikke fjernes og stikket må ikke trækkes ud, mens UPS'en er tændt. Dette fjerner sikkerhedsjorden fra UPS'en og fra det udstyr, der er sat til. 164201449 Rev B www.eaton.com/powerquality Eaton 5115 Rack-Mount UPS (500–1500 VA) User's Guide...
  • Page 11 Åbn eller ødelæg ikke batteriet eller batterierne. Udløst elektrolyt er skadeligt for hud og øjne og kan være yderst giftigt. Udskift batterierne med samme batterinummer og -type som de oprindeligt installerede i UPS'en. 164201449 Rev B www.eaton.com/powerquality Eaton 5115 Rack-Mount UPS (500–1500 VA) User's Guide...
  • Page 12: Belangrijke Veiligheidsinstructies

    Om aan de internationale normen en bedradingsvoorschriften te voldoen mag de gehele apparatuur die op de uitgang van deze UPS is aangesloten, geen aardlekstroom van meer dan 3,5 milliampère hebben. 164201449 Rev B www.eaton.com/powerquality Eaton 5115 Rack-Mount UPS (500–1500 VA) User's Guide...
  • Page 13 (kuten useimmissa eurooppalaisissa sovelluksissa) lähtövastakkeiden jännite on 0 V. Linjasta linjaan –tulojohdotuksessa lähtövastakkeiden jännite on 110–120V (mitataan linjasta maahan tai linjasta neutraaliin, UPS-virtalähteen johdotuksesta riippuen). 164201449 Rev B www.eaton.com/powerquality Eaton 5115 Rack-Mount UPS (500–1500 VA) User's Guide...
  • Page 14 Älä avaa tai vaurioita akkua tai akkuja. Paljastunut elektrolyytti on vahingollinen iholle ja silmille ja voi olla erittäin myrkyllistä. Vaihda UPS-virtalähteeseen vain samanlaiset akut ja sama määrä akkuja kuin siinä oli alun perin. 164201449 Rev B www.eaton.com/powerquality Eaton 5115 Rack-Mount UPS (500–1500 VA) User's Guide...
  • Page 15 Afin d'être conforme aux normes et règlements internationaux de câblage, le courant de fuite à la terre de la totalité du matériel branché sur la sortie de l'onduleur ne doit pas dépasser 3,5 mA. 164201449 Rev B www.eaton.com/powerquality Eaton 5115 Rack-Mount UPS (500–1500 VA) User's Guide...
  • Page 16 échappe est nuisible à la peau et aux yeux et peut s'avérer extrêmement toxique. Remplacez les batteries par des batteries du même type et numéro que celles installées à l'origine sur l'onduleur. 164201449 Rev B www.eaton.com/powerquality Eaton 5115 Rack-Mount UPS (500–1500 VA) User's Guide...
  • Page 17: Wichtige Sicherheitsanweisungen

    Die USV nicht in der Nähe von Wasser oder in extrem hoher Luftfeuchtigkeit (max. 95 %) betreiben. Um internationale Normen und Verdrahtungsvorschriften zu erfüllen, dürfen die an den Ausgang dieser USV angeschlossenen Geräte zusammen einen Erdableitstrom von insgesamt 3,5 Milliampere nicht überschreiten. 164201449 Rev B www.eaton.com/powerquality Eaton 5115 Rack-Mount UPS (500–1500 VA) User's Guide...
  • Page 18 Die Batterie(n) nicht öffnen oder baulich verändern. Ausfließendes Elektrolyt ist schädlich für Haut und Augen. Falls Sie die Batterien austauschen, verwenden Sie bitte ausschließlich die gleiche Anzahl und die Batterietypen. 164201449 Rev B www.eaton.com/powerquality Eaton 5115 Rack-Mount UPS (500–1500 VA) User's Guide...
  • Page 19: Avvisi Di Sicurezza

    Per conformità con gli standard internazionali e con le norme in merito al cablaggio, tutta l'apparecchiatura collegata con l'uscita del gruppo statico di continuità non deve avere una corrente di dispersione di terra superiore a 3,5 milliampere. 164201449 Rev B www.eaton.com/powerquality Eaton 5115 Rack-Mount UPS (500–1500 VA) User's Guide...
  • Page 20: Viktig Sikkerhetsinformasion

    0 V dersom din enhets strømkilde er fase-til-nøytral (som på de fleste europeiske enheter). Med ledningsført fase-til-fase inngang vil spenningen til utgangsstikkene være 110–120V (målt fra fase-til-jord eller fase-til-nøytral, avhenging av UPS-ledningsføringen). 164201449 Rev B www.eaton.com/powerquality Eaton 5115 Rack-Mount UPS (500–1500 VA) User's Guide...
  • Page 21 Et batteri eller batterier må ikke åpnes eller ødelegges. Frigjorte elektrolytter er skadelige for hud og øyne og kan være ekstremt giftige. Skift ut originalbatteriene i UPS-enheten med samme antall og type. 164201449 Rev B www.eaton.com/powerquality Eaton 5115 Rack-Mount UPS (500–1500 VA) User's Guide...
  • Page 22 Para estar de acordo com os padrões internacionais e os regulamentos de fiação, o equipamento total conectado à saída desta UPS não deve ter uma corrente de fuga à terra maior que 3,5 miliampères. 164201449 Rev B www.eaton.com/powerquality Eaton 5115 Rack-Mount UPS (500–1500 VA) User's Guide...
  • Page 23 Não abra nem danifique a(s) bateria(s). O eletrólito liberado é prejudicial à pele e aos olhos e pode ser extremamente tóxico. Ao realizar a troca das baterias, utilize a mesma quantidade e o mesmo tipo de bateria instalada originalmente no no-break. 164201449 Rev B www.eaton.com/powerquality Eaton 5115 Rack-Mount UPS (500–1500 VA) User's Guide...
  • Page 24 Äëÿ îáåñïå÷åíèÿ ñîáëþäåíèÿ òðåáîâàíèé ìåæäóíàðîäíûõ ñòàíäàðòîâ è òðåáîâàíèé ê ðàçâîäêå ýëåêòðè÷åñêèõ öåïåé, ñóììàðíàÿ âåëè÷èíà òîêà óòå÷êè íà çåìëþ âñåãî îáîðóäîâàíèÿ, ïîäêëþ÷åííîãî ê âûõîäó ÈÁÏ, íå äîëæíà ïðåâûøàòü 3,5 ìèëëèàìïåðà. 164201449 Rev B www.eaton.com/powerquality Eaton 5115 Rack-Mount UPS (500–1500 VA) User's Guide...
  • Page 25 âçîðâàòüñÿ ïîä âîçäåéñòâèåì îãíÿ. Íå äîïóñêàéòå âñêðûòèÿ èëè ïîâðåæäåíèÿ áàòàðåé. Âûòåêøèé ýëåêòðîëèò îïàñåí äëÿ êîæè è ãëàç è âûñîêîòîêñè÷åí. Çàìåíÿéòå áàòàðåè ÈÁÏ òîëüêî òàêèì æå êîëè÷åñòâîì áàòàðåé àíàëîãè÷íîãî òèïà. 164201449 Rev B www.eaton.com/powerquality Eaton 5115 Rack-Mount UPS (500–1500 VA) User's Guide...
  • Page 26: Advertencias De Seguridad

    Para cumplir con los estándares internacionales y las normas de instalación, la totalidad de los equipos conectados a la salida de este SIE no debe tener una intensidad de pérdida a tierra superior a los 3,5 miliamperios. 164201449 Rev B www.eaton.com/powerquality Eaton 5115 Rack-Mount UPS (500–1500 VA) User's Guide...
  • Page 27 Europa) är spänningen till de utgående uttagen 0 V. Är den ingående strömkällan kopplad ledare-till-ledare är spänningen i de utgående uttagen 110–120 V (uppmätt från ledare-till-jord eller ledare-till-nolla beroende på UPS:ens anslutning). 164201449 Rev B www.eaton.com/powerquality Eaton 5115 Rack-Mount UPS (500–1500 VA) User's Guide...
  • Page 28 Öppna eller förstör inte batteriet eller batterierna. Utsläppt elektrolyt är skadlig för hud och ögon och kan vara mycket giftig. Byt ut batterierna mot samma antal och typer av batterier som ursprungligen installerats i UPS-enheten. 164201449 Rev B www.eaton.com/powerquality Eaton 5115 Rack-Mount UPS (500–1500 VA) User's Guide...
  • Page 29: Installation

    NOTE Check the battery recharge date on the shipping carton label. If the date has expired and the batteries were never recharged, do not use the UPS. Contact your service representative. 164201449 Rev B www.eaton.com/powerquality Eaton 5115 Rack-Mount UPS (500–1500 VA) User's Guide...
  • Page 30: Connecting The Ups Internal Battery

    Figure 2. Removing the UPS Front Cover Remove the protective label from the internal battery connector (see Figure 3). Figure 3. Removing the Protective Label 164201449 Rev B www.eaton.com/powerquality Eaton 5115 Rack-Mount UPS (500–1500 VA) User's Guide...
  • Page 31: Ups Setup

    Continue to the following section, “UPS Setup.” UPS Setup The Eaton 5115 RM UPS is designed for flexible configurations and can be installed in a rack, on a wall, or as a standalone cabinet. Set up the UPS according to the type of installation: “Mounting the UPS in a 19”...
  • Page 32: Mounting The Ups In A 19" Rack

    UPS will be located and tighten the wing nut. Rear Hold-Down Bracket Rear Front Assembly Wing Nuts Wing Nut for Rear Hold-Down Bracket Rail Assembly Figure 7. Adjusting the Rail Depth 164201449 Rev B www.eaton.com/powerquality Eaton 5115 Rack-Mount UPS (500–1500 VA) User's Guide...
  • Page 33 Repeat Steps 6 through 8 for the other rail. 10. Tighten the assembly wing nuts on both rail assemblies. Assembly Wing Nuts Clip Nuts Front Rail Screw Figure 9. Securing the Front Rail 164201449 Rev B www.eaton.com/powerquality Eaton 5115 Rack-Mount UPS (500–1500 VA) User's Guide...
  • Page 34 12. Secure the front of the UPS to the rack using one M6 10 screw on each side as shown in Figure 10. 13. Adjust the rear hold-down brackets as needed. Figure 10. Securing the UPS in a 19” Rack 164201449 Rev B www.eaton.com/powerquality Eaton 5115 Rack-Mount UPS (500–1500 VA) User's Guide...
  • Page 35: Mounting The Ups In A 23" Rack

    Secure the front of the UPS to the rack using the supplied hardware (two M6 10 screws and two clip nuts on each side, as shown in Figure 12). Figure 12. Securing the UPS in a 23” Rack 164201449 Rev B www.eaton.com/powerquality Eaton 5115 Rack-Mount UPS (500–1500 VA) User's Guide...
  • Page 36: Zero-U Mounting

    Adjust the sides of the rack to fit the UPS and brackets (within 56.35–56.95 cm or 22.54–22.78”). Secure the UPS to the side of the rack cabinet using one M6 screw and one clip nut in each mounting bracket. 164201449 Rev B www.eaton.com/powerquality Eaton 5115 Rack-Mount UPS (500–1500 VA) User's Guide...
  • Page 37 INSTALLATION Side of Rack Cabinet (within 56.35–56.95 cm or 22.54–22.78”) Figure 13. Zero-U Mounting 164201449 Rev B www.eaton.com/powerquality Eaton 5115 Rack-Mount UPS (500–1500 VA) User's Guide...
  • Page 38: Wall-Mount Setup

    Secure the UPS to the wall using one bolt in each mounting bracket as shown. Select the bolt according to the wall type. Wall Figure 14. Mounting the UPS to a Wall 164201449 Rev B www.eaton.com/powerquality Eaton 5115 Rack-Mount UPS (500–1500 VA) User's Guide...
  • Page 39: Installing The Ups

    Four 5‐15 Receptacles Communication Bay Protector USB Port DIP Switches Site Wiring Fault Communication Indicator Port 6-ft Power Cord with 5‐15 Plug Figure 15. 500–1500 VA, 120V Rear Panel 164201449 Rev B www.eaton.com/powerquality Eaton 5115 Rack-Mount UPS (500–1500 VA) User's Guide...
  • Page 40 NOTE The batteries charge to 90% capacity in approximately 3 hours. However, it is recommended that the batteries charge for 6 to 24 hours after installation or long-term storage. 164201449 Rev B www.eaton.com/powerquality Eaton 5115 Rack-Mount UPS (500–1500 VA) User's Guide...
  • Page 41: Operation

    To turn on the UPS without using utility power, press and hold the button for two seconds. The UPS starts up in Battery mode and supplies battery power to your equipment. 164201449 Rev B www.eaton.com/powerquality Eaton 5115 Rack-Mount UPS (500–1500 VA) User's Guide...
  • Page 42: Turning The Ups Off

    The battery recharges when necessary. NOTE For 220–240V models, the output receptacles may remain electrically live (up to 110–120V). Unplug the UPS to ensure power is not available to the output receptacles. 164201449 Rev B www.eaton.com/powerquality Eaton 5115 Rack-Mount UPS (500–1500 VA) User's Guide...
  • Page 43: Ups Front Panel

    Press and hold the button for three seconds to initiate the self‐test. If the alarm beeps or a UPS alarm indicator stays on, see Table 8 on page 58. 164201449 Rev B www.eaton.com/powerquality Eaton 5115 Rack-Mount UPS (500–1500 VA) User's Guide...
  • Page 44 OPERATION 164201449 Rev B www.eaton.com/powerquality Eaton 5115 Rack-Mount UPS (500–1500 VA) User's Guide...
  • Page 45: Additional Ups Features

    Plug the UPS into a power outlet. To turn the UPS on, press and hold the button until you hear the UPS beep (approximately two seconds). UPS Rear Panel Figure 18. DIP Switches 164201449 Rev B www.eaton.com/powerquality Eaton 5115 Rack-Mount UPS (500–1500 VA) User's Guide...
  • Page 46: Network Transient Protector

    Connect the network or telephone (low voltage models only) cable to the jack labeled IN. Connect the input connector of the equipment you are protecting to the jack labeled OUT. Figure 19. Network Transient Protector 164201449 Rev B www.eaton.com/powerquality Eaton 5115 Rack-Mount UPS (500–1500 VA) User's Guide...
  • Page 47: Load Segments

    Load Segment 1 Load Segment 2 Figure 20. UPS Load Segments for 120V Models Load Segment 1 Load Segment 2 Figure 21. UPS Load Segments for 230V Models 164201449 Rev B www.eaton.com/powerquality Eaton 5115 Rack-Mount UPS (500–1500 VA) User's Guide...
  • Page 48 ADDITIONAL UPS FEATURES 164201449 Rev B www.eaton.com/powerquality Eaton 5115 Rack-Mount UPS (500–1500 VA) User's Guide...
  • Page 49: Communication

    Chapter 6 Communication The Eaton 5115 RM has flexible communication options for local, network, or remote monitoring and management. You can use the USB port or the DB-9 communication port to connect your computer to the UPS. The X-Slot communication bay is also available for additional connectivity options.
  • Page 50: Db-9 Communication Port

    To external device (tied to Pin 4) — No Connection — AC Fail AC Fail relay contact; 20 mA, 30 Vdc contact rating Power Source +V (8 to 24 volts DC power) 164201449 Rev B www.eaton.com/powerquality Eaton 5115 Rack-Mount UPS (500–1500 VA) User's Guide...
  • Page 51: X-Slot Cards

    X-Slot Cards X-Slot cards allow the UPS to communicate in a variety of networking environments and with different types of devices. The Eaton 5115 RM is compatible with the following X-Slot cards: ConnectUPS -X Web/SNMP Card - has SNMP and HTTP capabilities as well as monitoring through a Web browser interface;...
  • Page 52 COMMUNICATION 164201449 Rev B www.eaton.com/powerquality Eaton 5115 Rack-Mount UPS (500–1500 VA) User's Guide...
  • Page 53: Ups Maintenance

    Verify that the UPS is unplugged and turned off. Disconnect the UPS internal battery connector using the steps in “Connecting the UPS Internal Battery” on page 24 in reverse order. 164201449 Rev B www.eaton.com/powerquality Eaton 5115 Rack-Mount UPS (500–1500 VA) User's Guide...
  • Page 54: Storing The Ups And Batteries

    ELECTRIC ENERGY HAZARD. Do not attempt to alter any battery wiring or connectors. Attempting to alter wiring can cause injury. Replace batteries with the same number and type of batteries as originally installed in the UPS. 164201449 Rev B www.eaton.com/powerquality Eaton 5115 Rack-Mount UPS (500–1500 VA) User's Guide...
  • Page 55 Disconnect the internal battery connector (see Figure 26). Figure 26. Disconnecting the Internal Battery Connector Remove and set aside the battery cover (see Figure 27). Figure 27. Removing the Battery Cover 164201449 Rev B www.eaton.com/powerquality Eaton 5115 Rack-Mount UPS (500–1500 VA) User's Guide...
  • Page 56: Testing New Batteries

    If there is a problem with the battery, the alarm beeps, the indicator illuminates and the indicator flashes. Check the battery connections and be sure the battery is fully charged. Call your service representative if the problem persists. 164201449 Rev B www.eaton.com/powerquality Eaton 5115 Rack-Mount UPS (500–1500 VA) User's Guide...
  • Page 57: Recycling The Used Battery Or Ups

    C A U T I O N Do not discard waste electrical or electronic equipment (WEEE) in the trash. For proper disposal, contact your local recycling/reuse or hazardous waste center. 164201449 Rev B www.eaton.com/powerquality Eaton 5115 Rack-Mount UPS (500–1500 VA) User's Guide...
  • Page 58 UPS MAINTENANCE 164201449 Rev B www.eaton.com/powerquality Eaton 5115 Rack-Mount UPS (500–1500 VA) User's Guide...
  • Page 59: Specifications

    Efficiency (Normal mode) Noise Filtering Full-time EMI/RFI filtering Overcurrent Protection AC source overcurrent protection device Resettable input circuit protector Connections 6-ft, 5-15P power cord 10A, IEC-320 input connector 164201449 Rev B www.eaton.com/powerquality Eaton 5115 Rack-Mount UPS (500–1500 VA) User's Guide...
  • Page 60 CSA C22.2, No. 107.1; EN 50091-1-1 and IEC 60950 Safety Markings cULus, cUL cULus, cUL, CE, TÜV EMC (Class B) FCC Part 15, ICES-003 EN 50091-2, FCC Part 15, ICES-003 164201449 Rev B www.eaton.com/powerquality Eaton 5115 Rack-Mount UPS (500–1500 VA) User's Guide...
  • Page 61 Advanced monitoring for earlier failure detection and warning Battery Runtimes 5 minutes, typical at full load NOTE Battery times are approximate and may vary depending on the load configuration and battery charge. 164201449 Rev B www.eaton.com/powerquality Eaton 5115 Rack-Mount UPS (500–1500 VA) User's Guide...
  • Page 62 SPECIFICATIONS 164201449 Rev B www.eaton.com/powerquality Eaton 5115 Rack-Mount UPS (500–1500 VA) User's Guide...
  • Page 63: Troubleshooting

    (see Table 8). To silence the alarm for an existing fault, press the button. If UPS status changes, the alarm beeps, overriding the previous alarm silencing. 164201449 Rev B www.eaton.com/powerquality Eaton 5115 Rack-Mount UPS (500–1500 VA) User's Guide...
  • Page 64: Site Wiring Fault (120V Models Only)

    Prepare your equipment for shutdown. If this is an extended power outage, save your work and turn off your equipment to conserve battery power. 1 beep every 4 seconds. 164201449 Rev B www.eaton.com/powerquality Eaton 5115 Rack-Mount UPS (500–1500 VA) User's Guide...
  • Page 65 Clear vents and remove any heat sources. Ensure the airflow around the UPS is not restricted. Wait at Continuous beep. least 5 minutes and restart the UPS. If the condition persists, contact your service representative. 164201449 Rev B www.eaton.com/powerquality Eaton 5115 Rack-Mount UPS (500–1500 VA) User's Guide...
  • Page 66 Save your work and turn off your equipment. Turn off below or above the limit and unplug the UPS. Contact your service while the UPS is on representative. The alarm cannot be silenced. battery. Continuous beep. 164201449 Rev B www.eaton.com/powerquality Eaton 5115 Rack-Mount UPS (500–1500 VA) User's Guide...
  • Page 67: Service And Support

    A replacement or repair unit will be shipped, freight prepaid for all warrantied units. Help NOTE For critical applications, immediate replacement may be available. Call the Desk for the dealer or distributor nearest you. 164201449 Rev B www.eaton.com/powerquality Eaton 5115 Rack-Mount UPS (500–1500 VA) User's Guide...
  • Page 68 TROUBLESHOOTING 164201449 Rev B www.eaton.com/powerquality Eaton 5115 Rack-Mount UPS (500–1500 VA) User's Guide...
  • Page 69: Warranty

    This limited warranty (this “Warranty”) applies only to the original End-User (the “End-User”) of any Eaton 3105, 5110, 5115, 5125, and 5130 Products (individually and collectively, the “Product”) purchased on or after August 19, 2009 and cannot be transferred. This Warranty applies even in the event that the Product is initially sold by Company for resale to an End-User.
  • Page 70 Product is sold, Company shall have no obligation under this Warranty. Also during such time, the period of this Warranty shall continue to run and the expiration of this Warranty shall not be extended upon payment of any overdue or unpaid amounts. 164201449 Rev B www.eaton.com/powerquality Eaton 5115 Rack-Mount UPS (500–1500 VA) User's Guide...
  • Page 71: Load Protection Guarantee (Us And Canada)

    In the USA, call the Customer Reliability Center 7x24 at 800-356-5737. Outside of the USA, call your local Eaton product sales or service representative. For comments or questions about this Warranty, write to the Customer Quality Representative, 3301 Spring Forest Road, Raleigh, North Carolina 27616 USA.
  • Page 72 This Guaranty is not valid: (a) unless the End-User returns to Company the Warranty Registration Card or completes the registration form on www.eaton.com/PQ/Register within thirty (30) days of purchase; or (b) if the Product's serial numbers have been removed or are illegible.