To install an RMP:

6.2
NOTE: Before installing an RMP , be sure you have prepared the UPS according to
the instructions in paragraph 2.2.6.
1.
Securely mount the RMP(s).
2.
Install wiring from the RMP using ½-in. conduit through the cable entry
knockout in the top of the UPS Input/Rectifier cabinet (refer to Appendix A,
Drawing 164201244---7, for the location of the conduit landing area).
3.
In the spare parts kit, locate the RMP adapter cable assembly
(see Figure 6---2). Mate the DB---9 connector on the back of the terminal block
to the DB---9 connector (Port 1) on the Customer Interface Panel of the UPS
(refer to Drawing 164201244---2 in Appendix A). Use two screws from the
spare parts kit to secure the terminal block bracket to the Customer Interface
Panel.
Connect to
Port 1 (DB---9) on
Customer Interface Panel
Powerware 9315 (500 kVA- -750 kVA) Installation and Operation
164201244 REV. D 030101
Figure 6 ---2. Terminal Block Bracket
FUSE
TERMINAL
BLOCK
(TB3)
6--3