Powerware Prestige 9 Series User Manual

Powerware Prestige 9 Series User Manual

2500/3000 va, 200-240
Hide thumbs Also See for Prestige 9 Series:
Table of Contents

Advertisement

02/20/2001
®
powerware
9
Prestige Series
User's Guide
2500/3000 VA, 200-240V
www.powerware.com

Advertisement

Table of Contents
loading
Need help?

Need help?

Do you have a question about the Prestige 9 Series and is the answer not in the manual?

Questions and answers

Subscribe to Our Youtube Channel

Summary of Contents for Powerware Prestige 9 Series

  • Page 1 02/20/2001 ® powerware Prestige Series User’s Guide 2500/3000 VA, 200-240V www.powerware.com...
  • Page 2 Novell is a registered trademark of Novell, Inc. 3Com is a registered trademark of 3Com Corporation. Copyright 1994-99 Powerware Corporation, Raleigh, North Carolina. All rights reserved. No part of this document may be reproduced in any way without the express written approval of Powerware Corporation.
  • Page 3 UPS Q UICK NSTALLATION Cabinet Battery Cabinet Battery Breaker...
  • Page 4 UPS Quick Installation Power Strip The UPS output voltage is factory-configured for 230V. If you need to change the output voltage, see “UPS Startup” on page 32.
  • Page 5 UPS with PPDM Quick Installation PPDM Q WITH UICK NSTALLATION Cabinet Battery Cabinet PowerPass Distribution Module (PPDM, 60 Hz) Bypass Switch (NORMAL Position) Battery Breaker...
  • Page 6 UPS with PPDM Quick Installation The UPS output voltage is factory-configured for 230V. If you need to change the output voltage, see “UPS with Optional PowerPass Module Startup” on page 42.
  • Page 7 UPS with PPIM Quick Installation PPIM Q WITH UICK NSTALLATION UPS Cabinet PowerPass Isolation Module Battery Cabinet (PPIM, 50 Hz)
  • Page 8 UPS with PPIM Quick Installation Bypass Switch (NORMAL Position) Battery Breaker The UPS output voltage is factory-configured for 230V. If you need to change the output voltage, see “UPS with Optional PowerPass Module Startup” on page 42.
  • Page 9: Table Of Contents

    ............Powerware 9 Prestige Series User’s Guide (2500/3000 VA)
  • Page 10 ............Powerware 9 Prestige Series User’s Guide (2500/3000 VA)
  • Page 11: Introduction

    C H A P T E R 1 NTRODUCTION Congratulations on the purchase of your Powerware 9 9 Prestige Series uninterruptible power system (UPS). The Prestige UPS meets the toughest measures of superior design and manufacturing, including ISO 9001. You now own the most reliable power protection available.
  • Page 12: Ups Model And Battery Configurations

    (see Figure 2). If the load consists of the power-factor corrected supplies, it is recommended to use total watts for the load requirements. Powerware 9 Prestige Series User’s Guide (2500/3000 VA) www.powerware.com ®...
  • Page 13: Battery Times For The Prestige 3000

    36.8 27.6 1200 18.4 1600 1120 13.7 2000 1400 10.7 2500 1750 3000 2100 Typical Power Factor (PF) NOTE Battery times shown also apply to the Prestige 3000 with PPIM. Powerware 9 Prestige Series User’s Guide (2500/3000 VA) www.powerware.com ®...
  • Page 14: Battery Times For The Prestige 3000 With Ppdm

    Average Battery Time (in Minutes) Load (VA) Load (VA) Load (W) Load (W) 1 Cabinet 2 Cabinets 3 Cabinets 36.8 27.6 1200 18.4 1600 1067 13.7 2000 1333 10.7 2500 1667 3000 2000 Powerware 9 Prestige Series User’s Guide (2500/3000 VA) www.powerware.com ®...
  • Page 15: Special Symbols

    - Indicates the battery connector, BATTERY CONNECTOR which remains electrically “hot” even with the battery breaker off. Keep covered when not in use. - Indicates an output breaker. OUTPUT BREAKER Powerware 9 Prestige Series User’s Guide (2500/3000 VA) www.powerware.com ®...
  • Page 16 Introduction Powerware 9 Prestige Series User’s Guide (2500/3000 VA) www.powerware.com ®...
  • Page 17: Safety Warnings

    To reduce the risk of fire or electric shock, install this UPS in a temperature and humidity controlled, indoor environment, free of conductive contaminants. Ambient temperature must not exceed 104 F (40 C). Do not operate near water or • • excessive humidity (95% max). Powerware 9 Prestige Series User’s Guide (2500/3000 VA) www.powerware.com ®...
  • Page 18: Sikkerhedsanvisninger

    Korrekt bortskaffelse af batterier er påkrævet. Overhold gældende lokale regler for bortskaffelsesprocedurer. Denne UPS indeholder egen energiforsyning (batterier). Udgangsnetstikkene kan lede strøm, selv når UPS’en ikke er tilsat en AC-energikilde. Powerware 9 Prestige Series User’s Guide (2500/3000 VA) www.powerware.com ®...
  • Page 19 Med hensyn til Bypass-systemer med direkte forbundne udgange, skal overstrømsbeskyttelsen for AC-kredsen(e) komme andetsteds fra. Med hensyn til Bypass-systemer med direkte forbundne udgange, skal afbryderkontakter til AC-kredsløbet med passende mærkeeffekt komme andetsteds fra. Powerware 9 Prestige Series User’s Guide (2500/3000 VA) www.powerware.com ®...
  • Page 20: Belangrijke Veiligheidsinstructies

    De omgevingstemperatuur mag 40 C niet overschrijden. Niet gebruiken in de buurt van water of bij zeer hoge vochtigheid (max. 95%). Powerware 9 Prestige Series User’s Guide (2500/3000 VA) www.powerware.com ®...
  • Page 21: Tärkeitä Turvaohjeita

    MITÄÄN KÄYTTÄJÄN HUOLLETTAVIA OSIA. V A R O Akusto saattaa aiheuttaa sähköiskun tai syttyä tuleen, jos akusto kytketään oikosulkuun. Noudata asianmukaisia ohjeita. Akusto täytyy hävittää säädösten mukaisella tavalla. Noudata paikallisia määräyksiä. Powerware 9 Prestige Series User’s Guide (2500/3000 VA) www.powerware.com ®...
  • Page 22 ), riippumatta siitä, onko tulokaapeli kytkettynä tai ei. Tämän laitteen mukana ei toimiteta lähdön ylivirtasuojausta kiinteän asennuksen ohitusjärjestelmissä. Tämän laitteen mukana ei toimiteta lähdön johdonsuojakatkaisijoita jakeluja varten kiinteän asennuksen ohitusjärjestelmissä. Powerware 9 Prestige Series User’s Guide (2500/3000 VA) www.powerware.com ®...
  • Page 23: Consignes De Sécurité

    La température ambiante ne ° doit pas dépasser 40 C. Ne pas utiliser à proximité d’eau ou dans une atmosphère excessivement humide (95 % maximum). Powerware 9 Prestige Series User’s Guide (2500/3000 VA) www.powerware.com ®...
  • Page 24: Sicherheitswarnungen

    Batterien können aufgrund des hohen Kurzschlußstroms Elektroschocks oder Verbrennungen verursachen. Die entsprechenden Vorsichtsmaßnahmen sind unbedingt zu beachten. Die Batterien müssen ordnungsgemäß entsorgt werden. Hierbei sind die örtlichen Bestimmungen zu beachten.en. Powerware 9 Prestige Series User’s Guide (2500/3000 VA) www.powerware.com ®...
  • Page 25 Wenn das Gerät längere Zeit nicht benutzt wird, sollte es von der Netzsteckdose abgezogen werden. Beachten, daß die Ausgangssteckdosen auf der USV jedesmal Strom führen, wenn der Belastungsschalter ( ) gedrückt wird, ungeachtet dessen, ob die USV mit Strom versorgt wird. Powerware 9 Prestige Series User’s Guide (2500/3000 VA) www.powerware.com ®...
  • Page 26: Ðñïåéäïðïéþóåéò Áóöüëåéáò

    ÐïôÝ ìçí ðåôÜôå ôïõò óõóóùñåõôÝò óôç öùôéÜ, ãéáôß ìðïñåß íá åêñáãïýí. ÐïôÝ ìçí áíïßãåôå Þ êáôáóôñÝöåôå ôïõò óõóóùñåõôÝò. Ï çëåêôñïëýôçò ðïõ èá áðåëåõèåñùèåß ìðïñåß íá ðñïêáëÝóåé âëÜâç óôï äÝñìá êáé ôá ìÜôéá, êáé ìðïñåß íá åßíáé åîáéñåôéêÜ ôïîéêüò. Powerware 9 Prestige Series User’s Guide (2500/3000 VA) www.powerware.com ®...
  • Page 27 áðü ôçí õðåñÝíôáóç ãéá ôï êýêëùìá (ôá êõêëþìáôá) åîüäïõ AC ðñÝðåé íá ðáñÝ÷åôáé áðü ôñßôïõò. Óôá óõóôÞìáôá ÐáñÜêáìøçò ìå êáëùäéùìÝíåò åîüäïõò, ïé äéáêüðôåò áðïóýíäåóçò ðïõ åßíáé êáôÜëëçëïé ãéá ôï êýêëùìá (êõêëþìáôá) åîüäïõ AC ðñÝðåé íá ðáñÝ÷ïíôáé áðü ôñßôïõò. Powerware 9 Prestige Series User’s Guide (2500/3000 VA) www.powerware.com ®...
  • Page 28: Avvisi Di Sicurezza

    Assicurarsi che la spina di ingresso sia completamente inserita nella presa a muro. Usare esclusivamente una presa a corrente alternata monofase, a tre fili, collegata a terra. Powerware 9 Prestige Series User’s Guide (2500/3000 VA) www.powerware.com ®...
  • Page 29 Bypass provvisti di uscite cablate, i sezionatori di corrente nominale adeguata per il/i circuito/i a corrente alternata in uscita devono essere forniti da terzi. Powerware 9 Prestige Series User’s Guide (2500/3000 VA) www.powerware.com ®...
  • Page 30: Viktig Sikkerhetsinformasion

    Stikkontakten må befinne seg innen 2 m fra utstyret og må være tilgjengelig for operatøren. Av/På-bryteren på UPS’en isolerer ikke de interne delene. Trekk ut ledningen fra stikkontakten når utstyret frakoples over lengre tidsrom. Powerware 9 Prestige Series User’s Guide (2500/3000 VA) www.powerware.com...
  • Page 31: Regulamentos De Segurança

    Nunca jogue as baterias no fogo, porque há risco de explosão. Nunca abra ou danifique as baterias. O eletrólito liberado é prejudicial à pele e aos olhos e pode ser extremamente tóxico. Powerware 9 Prestige Series User’s Guide (2500/3000 VA) www.powerware.com...
  • Page 32 Para sistemas Bypass com saídas conectadas, interruptores de desconexão devidamente qualificados para circuitos de saída de corrente alternada devem ser fornecidos por outros. Powerware 9 Prestige Series User’s Guide (2500/3000 VA) www.powerware.com ®...
  • Page 33: Предупреждения По Мерам Безопасности

    время установки в том, что розетка оснащена средствами защиты от перегрузки по току. Убедитесь в том, что входная вилка надежно вставлена в настенную розетку. Пользуйтесь только однофазной трехпроводной заземленной розеткой переменного тока. Powerware 9 Prestige Series User’s Guide (2500/3000 VA) www.powerware.com ®...
  • Page 34 по току выходной(ых) цепи(ей) переменного тока должна обеспечиваться сторонними организациями. Для блока байпаса с неразъемными выходами сторонними организациями должны быть обеспечены выключатели выходной(ых) цепи(ей) переменного тока, рассчитанные на соответствующий номинал. Powerware 9 Prestige Series User’s Guide (2500/3000 VA) www.powerware.com ®...
  • Page 35: Advertencias De Seguridad

    La temperatura ambiente no debe exceder los 40 C. No trabaje cerca del agua o con humedad excesiva (95% máximo). Powerware 9 Prestige Series User’s Guide (2500/3000 VA) www.powerware.com ®...
  • Page 36: Säkerhetsföreskrifter

    ANVÄNDAREN KAN UTFÖRA SERVICE PÅ inuti UPS-enheten. V I K T I G T Batterierna kan ge elektriska stötar eller brännskador från hög kortslutningsström. Följ tillämpliga anvisningar. Batterierna måste avyttras enligt anvisningarna i lokal lagstiftning. Powerware 9 Prestige Series User’s Guide (2500/3000 VA) www.powerware.com ®...
  • Page 37 Överströmsskydd för de utgående växelströmkretsarna ska tillhandahållas av andra för fast anslutna förbikopplingssystem. Strömbrytare för bortkoppling med passande dimensioner för de utgående växelströmkretsarna ska tillhandahållas av andra för fast anslutna förbikopplingssystem. Powerware 9 Prestige Series User’s Guide (2500/3000 VA) www.powerware.com ®...
  • Page 38 Safety Warnings Powerware 9 Prestige Series User’s Guide (2500/3000 VA) www.powerware.com ®...
  • Page 39: Installation

    See “UPS with Do you have an Optional PowerPass optional PowerPass Module Installation” Module? on page 35. See the following section, “UPS and Battery Cabinet Installation.” Powerware 9 Prestige Series User’s Guide (2500/3000 VA) www.powerware.com ®...
  • Page 40: Ups And Battery Cabinet Installation

    OFF (O) position (see Figure 4). 3. Remove the battery connector guard. Plug the battery cord into the external battery connector on the UPS. All battery connectors are polarized to prevent incorrect connection. Powerware 9 Prestige Series User’s Guide (2500/3000 VA) www.powerware.com ®...
  • Page 41 8. Plug the optional output receptacle power strip or the optional Extended Power Distribution Module (EPDM 320-C20P) into the UPS power output receptacle (see Figure 4). Powerware 9 Prestige Series User’s Guide (2500/3000 VA) www.powerware.com ®...
  • Page 42: Ups Startup

    AC receptacle that has been wired in accordance with NEC specifications or national wiring rules. 3. Press the Output Off button until the alarm beeps. All indicators flash simultaneously. Powerware 9 Prestige Series User’s Guide (2500/3000 VA) www.powerware.com ®...
  • Page 43 NEC specifications or national wiring rules. 9. Turn on the equipment that is connected to the UPS. 10. Press and hold the Output On button until you hear the UPS beep (approximately one second). Powerware 9 Prestige Series User’s Guide (2500/3000 VA) www.powerware.com ®...
  • Page 44: Repo Installation

    2. Pivot the REPO receptacle guard out of the way, plug the REPO plug/receptacle UPS connector into the REPO receptacle on the UPS rear panel and twist the connector in place (see Figure 4 on page 31). Powerware 9 Prestige Series User’s Guide (2500/3000 VA) www.powerware.com ®...
  • Page 45: Ups With Optional Powerpass Module Installation

    1. Place the UPS near the equipment to be protected. The UPS should be well ventilated and away from direct sunlight or other heat source. Figure 7 and Figure 8 show the UPS stacking configurations with the PPDM and PPIM, respectively. Powerware 9 Prestige Series User’s Guide (2500/3000 VA) www.powerware.com ®...
  • Page 46 Installation Cabinet Air Vents Battery Cabinet PPDM Figure 7. Distribution Module Setup Cabinet Air Vents Battery PPIM Cabinet Figure 8. Isolation Module Setup Powerware 9 Prestige Series User’s Guide (2500/3000 VA) www.powerware.com ®...
  • Page 47 Battery Connector Breaker Tie Battery Cord Battery Cabinet Bypass Y-Cord Switch Power Output Load Circuit Receptacles Protectors Utility Input Connector PPDM (60 Hz) Figure 9. UPS with PPDM Rear Panel Powerware 9 Prestige Series User’s Guide (2500/3000 VA) www.powerware.com ®...
  • Page 48 6. Remove the breaker tie from the circuit breaker on all battery cabinets. 7. Switch the circuit breaker on all battery cabinets to the ON ( position. Powerware 9 Prestige Series User’s Guide (2500/3000 VA) www.powerware.com ®...
  • Page 49 Only qualified service personnel (such as a licensed electrician) should perform the hardwired installation. 17. Remove the three screws on the terminal block access cover with a Phillips screwdriver and remove the cover (see Figure 11). Powerware 9 Prestige Series User’s Guide (2500/3000 VA) www.powerware.com ®...
  • Page 50 Figure 12 for the 60-Hz hardwired PPDM wiring or Figure 13 for the 50-Hz hardwired PPIM wiring. Input Output 208V/240V 120V Ground Ground Line 1 Neutral Line 2/Neutral Line 2 Line 1 Figure 12. 60-Hz Hardwired PPDM Terminal Block Powerware 9 Prestige Series User’s Guide (2500/3000 VA) www.powerware.com ®...
  • Page 51 21. If you are using a Remote Emergency Power-Off switch, follow the instructions in “REPO Installation” on page 34. 22. Start the UPS according to the following “UPS with Optional PowerPass Module Startup” procedure. Powerware 9 Prestige Series User’s Guide (2500/3000 VA) www.powerware.com ®...
  • Page 52: Ups With Optional Powerpass Module Startup

    All indicators flash simultaneously. 4. If your PowerPass Module is a plug/receptacle unit, plug the input power supply cord into the utility input connector on the PowerPass Module rear panel. Powerware 9 Prestige Series User’s Guide (2500/3000 VA) www.powerware.com ®...
  • Page 53 PowerPass Module rear panel. Plug the other end of the power supply cord into a grounded, three-wire, AC receptacle that has been wired in accordance with NEC specifications or national wiring rules. Powerware 9 Prestige Series User’s Guide (2500/3000 VA) www.powerware.com ®...
  • Page 54: Troubleshooting Tips

    UPS may need to operate for approximately 8 hours before the battery is fully charged and full battery-backup time is available. If the Battery Fault indicator flashes, operate the UPS for 24 hours to fully charge the battery. Powerware 9 Prestige Series User’s Guide (2500/3000 VA) www.powerware.com ®...
  • Page 55: Ups Operation

    Indicator Legend Sine Wave Indicator Unlit Amber Overload Indicator Green Site Fault Indicator Flashing Overtemp Indicator Battery Fault Indicator Self Test Indicator Battery Online Indicator Figure 15. UPS Front Panel Powerware 9 Prestige Series User’s Guide (2500/3000 VA) www.powerware.com ®...
  • Page 56: Operating Modes

    SELF TEST LOAD ON LOAD ON LOAD ON LOAD ON LOAD OFF APPROX. APPROX. APPROX. APPROX. NORMAL 81-100% 61-80% 41-60% 0-40% UTILITY LOAD LOAD LOAD LOAD Figure 17. Normal Operation Indicators Powerware 9 Prestige Series User’s Guide (2500/3000 VA) www.powerware.com ®...
  • Page 57: Bypass Mode

    If battery capacity becomes low while in Battery mode, the Battery Fault indicator begins to flash and the Self Test indicator remains lit, indicating approximately two minutes before UPS shutdown. The alarm beeps every two seconds. Powerware 9 Prestige Series User’s Guide (2500/3000 VA) www.powerware.com ®...
  • Page 58: Diagnostics

    The UPS supplies power to your equipment and goes into Battery mode. indicator remains lit and the front panel displays the percentage of battery capacity remaining to the UPS. This process should take about 15 seconds. Powerware 9 Prestige Series User’s Guide (2500/3000 VA) www.powerware.com ®...
  • Page 59: Ups Shutdown

    1. Perform a UPS shutdown as described in the previous section. 2. Follow the instructions in “UPS Startup” on page 32. If you have a PowerPass Module, see “UPS with Optional PowerPass Module Startup” on page 42. Powerware 9 Prestige Series User’s Guide (2500/3000 VA) www.powerware.com ®...
  • Page 60: Using The Powerpass Module

    Figure 20 and Figure 21 show the operation of the UPS with the PPDM or PPIM. Utility Power UPS Load PPDM Battery Battery Battery Figure 20. UPS and PPDM Block Diagram Powerware 9 Prestige Series User’s Guide (2500/3000 VA) www.powerware.com ®...
  • Page 61: Using Maintenance Bypass

    UPS shuts down. 4. Switch the circuit breaker on all battery cabinets to the OFF (O) position. 5. Disconnect the battery connector on the UPS rear panel. 6. Remove the UPS. Powerware 9 Prestige Series User’s Guide (2500/3000 VA) www.powerware.com ®...
  • Page 62 UPS Operation Power Input Connector Battery Connector Power Output Receptacle UPS Cabinet Battery Circuit Breaker Battery Cabinet Bypass Y-Cord Switch PPDM (60 Hz) Figure 22. UPS with PowerPass Module Rear Panel Powerware 9 Prestige Series User’s Guide (2500/3000 VA) www.powerware.com ®...
  • Page 63 Y-cord of the PowerPass Module into the power connectors on the UPS as shown in Figure 22. Release the Output Off button when the alarm beeps. All indicators flash simultaneously. Powerware 9 Prestige Series User’s Guide (2500/3000 VA) www.powerware.com ®...
  • Page 64 UPS as shown in Figure 22. 10. Press and hold the Output On button until you hear the UPS beep (approximately one second). indicator remains lit and the Self Test indicator turns Powerware 9 Prestige Series User’s Guide (2500/3000 VA) www.powerware.com ®...
  • Page 65 11. Turn the Bypass switch on the PowerPass Module to the NORMAL position. The front panel displays the percentage of full load being applied to the UPS. The UPS is now in Normal mode with the load online. Powerware 9 Prestige Series User’s Guide (2500/3000 VA) www.powerware.com ®...
  • Page 66 UPS Operation Powerware 9 Prestige Series User’s Guide (2500/3000 VA) www.powerware.com ®...
  • Page 67: Communication

    74. Help Desk If you want to change the UPS configuration settings, use the front panel or the UPS Serial Communications Menu. Powerware 9 Prestige Series User’s Guide (2500/3000 VA) www.powerware.com ®...
  • Page 68: Front Panel Communications Access

    Novell Contacts Select this mode for the OnliSafe software. OVERLOAD OVERLOAD SITE FAULT SITE FAULT OVERTEMP OVERTEMP BATTERY BATTERY SELF TEST SELF TEST Figure 24. Front Panel Communication Options Powerware 9 Prestige Series User’s Guide (2500/3000 VA) www.powerware.com ®...
  • Page 69 6. Press the Output On button again to return the UPS to Normal mode. NOTE Printer mode selections are the only serial communication modes available from the front panel. Powerware 9 Prestige Series User’s Guide (2500/3000 VA) www.powerware.com ®...
  • Page 70: Ups Serial Communications Menu

    D > Display Configuration settings and the new settings that you have selected prior to saving them. The new settings are not effective until you select save from the Main Menu. Powerware 9 Prestige Series User’s Guide (2500/3000 VA) www.powerware.com ®...
  • Page 71 The UPS prints the formatted data on the P > Printer Dump attached printer. allows you to configure the UPS for a new L > LAN Configuration LAN mode and displays the Select LAN Configuration Menu. Powerware 9 Prestige Series User’s Guide (2500/3000 VA) www.powerware.com ®...
  • Page 72 VUDGfA6DG v† hp‡v‰r ‚ƒr GPXf76UU v† hp‡v‰r py‚†rq " VUDGfA6DG v† hp‡v‰r py‚†rq GPXf76UU v† hp‡v‰r ‚ƒr VUDGfA6DG v† hp‡v‰r ‚ƒr GPXf76UU v† hp‡v‰r ‚ƒr UP RVDU UCDT H@IV @IU@S T@G@8UDPI 323 Powerware 9 Prestige Series User’s Guide (2500/3000 VA) www.powerware.com ®...
  • Page 73: Power Management Software

    If you have any questions or would like further information, call the Help Desk at one of the telephone numbers on page 74. Powerware 9 Prestige Series User’s Guide (2500/3000 VA) www.powerware.com ®...
  • Page 74: Ups Communications Interface Port

    50 feet (15m). See Figure 25 for the location of the serial port. UPS Rear Panel Serial Port Serial Port Detail Figure 25. Serial Port Location Powerware 9 Prestige Series User’s Guide (2500/3000 VA) www.powerware.com ®...
  • Page 75: Communications Mode Reference Chart

    Closed Bypass UPS Offline 17/19 Closed Low Battery Low Battery 23/24 Closed Signal Ground 12/15/18/25 NOTE Pin numbers separated by a forward slash ( / ) are connected together internally. Powerware 9 Prestige Series User’s Guide (2500/3000 VA) www.powerware.com ®...
  • Page 76 Communication Powerware 9 Prestige Series User’s Guide (2500/3000 VA) www.powerware.com ®...
  • Page 77: Specifications

    142.5 mm (5.61 in) Depth 400 mm (15.75 in) 400 mm (15.75 in) 400 mm (15.75 in) Weight 7.4 kg (16.25 lb) 23.6 kg (52 lb) 21.4 kg (47 lb) Powerware 9 Prestige Series User’s Guide (2500/3000 VA) www.powerware.com ®...
  • Page 78: Model 2500 Specifications With The 60-Hz Ppdm

    (Total not to exceed 1750 Watts, 2500 VA) Voltage In:Out Voltage In:Out Current Current IEC-320-C19/IEC-320-C13 Hardwired 208:208 10.9A 12.0A/10.0A 12.0A 220:220 10.3A 11.4A/10.0A 11.4A 230:230 9.8A 10.9A/10.0A 10.9A 240:240 9.4A 10.4A/10.0A 10.4A Powerware 9 Prestige Series User’s Guide (2500/3000 VA) www.powerware.com ®...
  • Page 79: Model 3000 Specifications With The 60-Hz Ppdm

    (Total not to exceed 2100 Watts, 3000 VA) Voltage In:Out Voltage In:Out Current Current IEC 320-C19/IEC 320-C13 Hardwired 220:220 12.9A 13.6A/10.0A 13.6A 230:230 12.3A 13.0A/10.0A 13.0A 240:240 11.9A 12.5A/10.0A 12.5A Powerware 9 Prestige Series User’s Guide (2500/3000 VA) www.powerware.com ®...
  • Page 80: Prestige 3000 Ups Technical Specifications

    Operating Environment Temperature: 10 C to 40 • • F to 104 Humidity: 5 to 95% (noncondensing) Agency Approvals Safety: EN50091-1 UL 1778 EMC: FCC Part 15 Class A EN50091-2 Powerware 9 Prestige Series User’s Guide (2500/3000 VA) www.powerware.com ®...
  • Page 81: Troubleshooting

    UPS does not provide Low battery capacity. Allow battery to charge for 24 hours, the expected backup then retest. time. Protected equipment power Reduce load, then retest. requirements exceed UPS capacity. Powerware 9 Prestige Series User’s Guide (2500/3000 VA) www.powerware.com ®...
  • Page 82 Battery breaker is open (O). Make sure the battery cabinet breaker is in the ON ( ) position. Battery cabinet is not properly Make sure battery cords are connected to the UPS. connected. Powerware 9 Prestige Series User’s Guide (2500/3000 VA) www.powerware.com ®...
  • Page 83: Resetting The Ups

    Output On button for one second. The alarm becomes quiet. If UPS status changes, the alarm beeps, overriding previous alarm silencing. Press the Output On button again to silence the alarm. Powerware 9 Prestige Series User’s Guide (2500/3000 VA) www.powerware.com...
  • Page 84: Service And Support

    Proof and Date of Purchase must be returned with the failed unit. For critical applications, immediate replacement may be available. Call for the dealer or distributor nearest you. Help Desk Powerware 9 Prestige Series User’s Guide (2500/3000 VA) www.powerware.com ®...
  • Page 85: Index

    63 battery contact configuration, serial port, 64 circuit breaker, 31 Continuous Dump Mode, 61 configuration, 2 extension time, 3 Control Keys input connector, 31 Control-C, 60 installation, 30 Control-E, 61 Powerware 9 Prestige Series User’s Guide (2500/3000 VA) www.powerware.com ®...
  • Page 86 Main, 60 Serial Communications, 60 Set Baud Rate, 63 Mode hardwired PowerPass Module ASCII Terminal, 61 rear panel, 40 Battery, 47 termination blocks, 40 Bypass, 47 Help Desk, 74 Communications, 60 Powerware 9 Prestige Series User’s Guide (2500/3000 VA) www.powerware.com ®...
  • Page 87 40 Overload plug/receptacle, 38 condition, 72 startup, 42 indicator, 45 utility input connector, 38 Overtemperature Printer Mode alarm, 72 front panel configuration, 59 indicator, 45 Main Menu configuration, 61 Powerware 9 Prestige Series User’s Guide (2500/3000 VA) www.powerware.com ®...
  • Page 88 31 Smart Dump Mode, 61 power output receptacles, 31 rear panel, 31 specifications, 67 resetting, 73 Startup Tests, 48 Serial Communications Menu, 60 storage temperature, 29 serial port, 31, 64 Powerware 9 Prestige Series User’s Guide (2500/3000 VA) www.powerware.com ®...
  • Page 89 Index shutdown, 49 special symbols, 5 startup, 32 storage, 29 unpacking and inspection, 29 UTIL_FAIL, 62 Utility Out of Spec, 72 volt-amperes, 2 VT100 Terminal Mode, 61 Powerware 9 Prestige Series User’s Guide (2500/3000 VA) www.powerware.com ®...
  • Page 90 Index Powerware 9 Prestige Series User’s Guide (2500/3000 VA) www.powerware.com ®...

Table of Contents