To install an RMP:

5.2
NOTE: 1. Before installing an RMP , be sure you have prepared the UPS according to
the instructions in paragraph 2.2.7.
2. If mounting to a hollow wall, secure the enclosure bottom to a wood or
metal stud within the wall. Do not use hollow wall anchors. The RMP also
has provisions to be mounted to a single or double gang wall electrical box.
1.
If wall mounting, securely mount the RMP . If desk mounting, install provided
bumpers to the bottom of the RMP enclosure.
2.
Install the Remote Monitor Card into an open x---slot on the rear panel of the
UPS Cabinet, using supplied hardware.
3.
If wall mounting, proceed to step 4; if desk mounting, proceed to step 5.
4.
Install wiring from the RMP to the UPS using ½-in. conduit through the cable
exit openings in the Remote Monitor Card (see Figure 5---2) and the RMP (refer
to Drawing 164201300---19 in Appendix A). Proceed to step 6.
5.
Install wiring from the RMP to the UPS using cable listed in Table 5---1 and
provided strain relief bushings in the cable exit openings in the Remote
Monitor Card (see Figure 5---2) and the RMP (refer to Drawing 164201300---19
in Appendix A).
6.
Connect wiring between the RMP and the UPS Remote Monitor Card plug-in
terminal blocks using terminations shown in Table 5---1. See Figures 5---2 and
5---3 for plug-in terminal block locations.
From RMP
7.
To check the operation of the RMP , ensure that the UPS system is supplying
the load via the inverter or bypass. If the indicators on the RMP show the
appropriate status, then it is operating correctly.
If the RMP is not operating correctly, check the wiring, the fuse on the Remote
Monitor Card, and the plug-in terminal blocks for proper seating. If all
connections are secure but the RMP still does not operate correctly, replace
the fuse. If this does not correct the problem, contact your local field service
office for verification that the RMP is working correctly.
5--2
Table 5---1. RMP Wire Terminations
Remote Monitor Card
J1---1
J1---3
J1---4
J1---5
J1---6
To UPS
J1---1
J1---3
Use Belden 8690 060
U
J1---4
or equivalent Cable
or equivalent Cable
J1---5
J1---6
Powerware 9330 (10 kVA- -40 kVA) Installation and Operation
Remarks
B ld
8690 060
164201300 REV. G 061502