Powerware 9315 UPS Operation Manual

Powerware 9315 UPS Operation Manual

200–300 kva
Hide thumbs Also See for 9315 UPS:
Table of Contents

Advertisement

Powerware 9315 UPS
®
200–300 kVA
Operation Manual

Advertisement

Table of Contents
loading

Summary of Contents for Powerware 9315 UPS

  • Page 1 Powerware 9315 UPS ® 200–300 kVA Operation Manual...
  • Page 2: Save These Instructions

    This is a product for restricted sales distribution to informed partners. Installation restrictions or additional measures may be needed to prevent disturbances. Powerware and X−Slot are registered trademarks and ConnectUPS is a trademark of Eaton Electrical Inc. Modbus is a registered trademark of Modicon.
  • Page 3: Table Of Contents

    ............. Monitoring and Controlling UPS Operation 9315 UPS (200–300 kVA) Operation Manual S 164201036 Rev G www.powerware.com EATON Powerware ®...
  • Page 4 ............9315 UPS (200–300 kVA) Operation Manual S 164201036 Rev G www.powerware.com ®...
  • Page 5 ............. . 9315 UPS (200–300 kVA) Operation Manual S 164201036 Rev G www.powerware.com EATON Powerware ®...
  • Page 6 ............Figure 5-2. Parts of the LCD Screen (Typical for Powerware 9315 300 480/480V UPS) Figure 5-3.
  • Page 7: Introduction

    The Powerware 9315 UPS continually monitors incoming electrical power and removes the surges, spikes, sags, and other irregularities that are inherent in commercial utility power. Working with your building’s electrical system, the UPS supplies clean, consistent power that your sensitive electronic equipment requires for reliable operation.
  • Page 8: For More Information

    Introduction 1.2 For More Information Refer to the Powerware 9315 UPS (200–300 kVA) Installation Manual for the following additional information: How to prepare your site and plan for installation Detailed step-by-step procedures for installing each component of your system Detailed illustrations of cabinets and optional accessories, including dimensions and connection points Visit www.powerware.com or contact your Eaton service representative for information on...
  • Page 9: Getting Started

    Do not operate the UPS system close to gas or electric heat sources. The operating environment should be maintained within the parameters stated in this manual. The UPS system is not intended for outdoor use. 9315 UPS (200–300 kVA) Operation Manual S 164201036 Rev G www.powerware.com EATON Powerware ® IMPORTANT SAFETY INSTRUCTIONS...
  • Page 10: Typical Powerware 9315 Ups System

    UPS switches, controls, or optional components. 2−2 EATON Powerware Battery Input Cabinet Transformer (optional) Cabinet 9315 UPS (200–300 kVA) Operation Manual S 164201036 Rev G www.powerware.com ® Output Transformer Cabinet Cabinet (optional– (optional) requires 480/208...
  • Page 11: Looking Inside The Ups

    2.3 Looking Inside the UPS The Powerware 9315 is a continuous−duty, solid-state UPS that supports the following equipment: process control, data processing, telecommunications/PBX, research, and medical. The Powerware 9315 maintains power to the critical loads during commercial electrical power brownout, blackout, overvoltage, undervoltage, and out-of-tolerance frequency conditions.
  • Page 12: Ups Standard Features

    The filter also reduces input harmonic current distortion and minimizes upstream interference that can damage sensitive hardware components. 2−4 EATON Powerware . See Chapter 7, Communication" for additional ® 9315 UPS (200–300 kVA) Operation Manual S 164201036 Rev G www.powerware.com ®...
  • Page 13: Emergency Load Off

    Several battery capacities are available. The UPS battery cabinets can be paralleled; you can increase the battery backup time by adding battery cabinets to your UPS system. The Powerware 9315 can support up to four battery cabinets. 2.5.2 External Battery Disconnect An optional DC circuit breaker, enclosed in a wall-mounted box adjacent to the UPS, provides a manual means of disconnecting a battery that is located remotely from the UPS.
  • Page 14: Power Distribution Module (Lv Models Only)

    An optional 480/480 Vac 5% input filter reduces input harmonic current distortion and minimizes upstream interference that can damage sensitive hardware components. The filter is contained in a separate cabinet. 2−6 EATON Powerware 9315 UPS (200–300 kVA) Operation Manual S 164201036 Rev G www.powerware.com ®...
  • Page 15: Output Transformer

    2.5.11 Customer Convenience Outlet An uninterruptible 120 Vac, 0.2A, fuse-protected convenience outlet is provided to supply power to the optional modem. It is located adjacent to the Communication Panel. 9315 UPS (200–300 kVA) Operation Manual S 164201036 Rev G www.powerware.com EATON Powerware ®...
  • Page 16: Symbols, Controls, And Indicators

    This symbol indicates that you should not discard waste electrical or electronic equipment (WEEE) in the trash. For proper disposal, contact your local recycling/reuse or hazardous waste center. 2−8 EATON Powerware 9315 UPS (200–300 kVA) Operation Manual S 164201036 Rev G www.powerware.com ®...
  • Page 17: Understanding Ups Operation

    Normal" appears in the status area of the LCD screen. Figure 3-1 shows the path of electrical power through the UPS system when the UPS is operating in Normal mode. 9315 UPS (200–300 kVA) Operation Manual S 164201036 Rev G www.powerware.com EATON Powerware ®...
  • Page 18: Figure 3-1. Path Of Current Through The Ups In Normal Mode

    If the UPS suffers an internal failure, it switches automatically to Bypass mode and remains in that mode until the failure is corrected and the UPS is back in service. 3−2 EATON Powerware Bypass Rectifier Inverter Battery 9315 UPS (200–300 kVA) Operation Manual S 164201036 Rev G www.powerware.com ® Output (Closed) Transformer...
  • Page 19: Bypass Mode

    Bypass mode is a normal operating mode, and not an alarm condition. However, if the UPS is unable to return to Normal mode following an automatic transfer to Bypass mode, an alarm condition is recorded. 9315 UPS (200–300 kVA) Operation Manual S 164201036 Rev G www.powerware.com EATON Powerware ®...
  • Page 20: Battery Mode

    The rectifier gradually draws increasing power from the incoming utility until Normal mode is achieved. 3−4 EATON Powerware Bypass Rectifier Inverter Battery 9315 UPS (200–300 kVA) Operation Manual S 164201036 Rev G www.powerware.com ® Output (Closed) Transformer...
  • Page 21: Monitoring And Controlling Ups Operation

    These control power to and from the UPS, and allow you to change the UPS mode manually. The Control Panel is discussed in Using the Control Panel" on page 4−1. 9315 UPS (200–300 kVA) Operation Manual S 164201036 Rev G www.powerware.com 3−5 EATON Powerware ®...
  • Page 22 Understanding UPS Operation This page intentionally left blank. 9315 UPS (200–300 kVA) Operation Manual S 164201036 Rev G www.powerware.com 3−6 EATON Powerware ®...
  • Page 23: Starting And Stopping The Ups

    Incorrect use of the power controls on the Control Panel can cause a loss of power to the protected equipment. 9315 UPS (200–300 kVA) Operation Manual S 164201036 Rev G www.powerware.com EATON Powerware ®...
  • Page 24: Resetting The Ups System After Load Off

    The rectifier turns on, then the inverter turns on. The UPS display and alarm alert you to close the battery breaker. 7. Close the battery breaker(s). 4−2 EATON Powerware 9315 UPS (200–300 kVA) Operation Manual S 164201036 Rev G www.powerware.com ®...
  • Page 25: To Shut Down The Ups From Normal Mode

    To perform maintenance or service on the critical load, you must shut it down first: 1. Turn off all equipment that is being powered through the UPS. 2. Press the LOAD OFF button on the Monitor Panel. 9315 UPS (200–300 kVA) Operation Manual S 164201036 Rev G www.powerware.com EATON Powerware ®...
  • Page 26 Starting and Stopping the UPS This page intentionally left blank. 9315 UPS (200–300 kVA) Operation Manual S 164201036 Rev G www.powerware.com 4−4 EATON Powerware ®...
  • Page 27: Using The Monitor Panel

    (4). A quick reference label describing how to use the Monitor Panel is located inside the UPS above the Control Panel. The following sections describe the Monitor Panel in detail. 9315 UPS (200–300 kVA) Operation Manual S 164201036 Rev G www.powerware.com EATON Powerware ®...
  • Page 28: Using The Lcd Screen

    Meters Events Statistics Graphics Setup Figure 5-2. Parts of the LCD Screen (Typical for Powerware 9315 300 480/480V UPS) The UPS status area contains three lines that display the current state of the UPS. The first line shows the present operational mode of the UPS. The second line shows the highest level of the current active alarms, and the third line shows any notices the UPS has posted.
  • Page 29: Using The Buttons

    All power to the critical load is lost when you press the LOAD OFF button. You should use the LOAD OFF button only when you want to de-energize the critical load. 9315 UPS (200–300 kVA) Operation Manual S 164201036 Rev G www.powerware.com EATON Powerware ®...
  • Page 30: Reading The Status Indicators

    Normal indicator is lit. During normal shutdown, the Standby indicator is lit until all energy in the UPS is dissipated and shutdown is complete. 9315 UPS (200–300 kVA) Operation Manual S 164201036 Rev G www.powerware.com ® buttons...
  • Page 31: Figure 5-3. System Meters Screen (Typical For Powerware 9315 300 480/480V Ups)

    Meters Events Statistics Graphics Setup Figure 5-3. System Meters Screen (Typical for Powerware 9315 300 480/480V UPS) The Input area shows the phase-to-phase voltage, frequency, and phase current of the incoming utility, followed by the kVA, KW, and power factor measurements. The output area shows the same information for the power being output by the UPS.
  • Page 32: Figure 5-4. Load Amps Meters Screen

    Events Statistics Graphics Setup 5−6 EATON Powerware Uninterruptible Power System Output Current 125% 100% Phase A Phase B Figure 5-4. Load Amps Meters Screen 9315 UPS (200–300 kVA) Operation Manual S 164201036 Rev G www.powerware.com ® 04 NOV 1997 14:23:45 Phase C...
  • Page 33: Figure 5-5. Event History Log Screen

    When the scroll bar is in the menu box, the return arrow is in the information area. When the scroll bar is in the information area, you can press the through the Event History log. 9315 UPS (200–300 kVA) Operation Manual S 164201036 Rev G www.powerware.com EATON Powerware ®...
  • Page 34: Figure 5-6. Active System Events Screen

    Shutdown Imminent Active System Events NOTICE: Input power unavailable NOTICE: Bypass Not Available ALARM: Shutdown Imminent Statistics Graphics Setup Figure 5-6. Active System Events Screen 9315 UPS (200–300 kVA) Operation Manual S 164201036 Rev G www.powerware.com ® 04 NOV 1997 14:23:45...
  • Page 35: Figure 5-7. Unit Statistics Screen

    UPS was on bypass, battery, or generator, and the amount of time the UPS logic has been functioning since the start date. The lower right column shows the percent of availability of the UPS and the bypass source. 9315 UPS (200–300 kVA) Operation Manual S 164201036 Rev G www.powerware.com EATON Powerware ®...
  • Page 36: Figure 5-8. Mimic Screen

    The Mimic screen shows the internal components of the UPS cabinet. The flow of current through the components is highlighted. 5−10 EATON Powerware Uninterruptible Power System Bypass Rectifier Battery Graphics Setup Figure 5-8. Mimic Screen 9315 UPS (200–300 kVA) Operation Manual S 164201036 Rev G www.powerware.com ® 04 NOV 1997 14:23:45 Inverter...
  • Page 37: Figure 5-9. Time Setup Screen

    If you want to save the settings upon exit from this screen, be sure the SAVE field is set to YES. 9315 UPS (200–300 kVA) Operation Manual S 164201036 Rev G www.powerware.com EATON Powerware ® Uninterruptible Power System Set Time &...
  • Page 38: Figure 5-10. Setup Serial Port 1 Screen

    Figure 5-10. Setup Serial Port 1 Screen ) appears in the upper right corner of the Port Setup screen. button. To save the settings upon exit from this screen, be sure 9315 UPS (200–300 kVA) Operation Manual S 164201036 Rev G www.powerware.com ® 04 NOV 1997...
  • Page 39: Using Features And Options

    Regardless of how you assign the building alarms, they display as Building Alarm 1, Building Alarm 2, Building Alarm 3, etc., on the LCD screen of the Monitor Panel. You should use twisted−pair wires for each alarm input and common. 9315 UPS (200–300 kVA) Operation Manual S 164201036 Rev G www.powerware.com EATON Powerware ®...
  • Page 40: Summary Alarm Contacts

    Contacts should not be operated in excess of 30 Vac or 42.4V peak AC or DC @ 1A maximum. 6−2 EATON Powerware ALARM NO ALARM NC COMMON NOTICE NO NOTICE NC COMMON Figure 6-2. Summary Alarm Contacts C A U T I O N 9315 UPS (200–300 kVA) Operation Manual S 164201036 Rev G www.powerware.com ®...
  • Page 41: Remote Monitor Panel

    (RMPs, Relay Interface Modules, or Supervisory Contact Modules) can be installed. See Table 6-1 for the number of accessories permitted. Figure 6-3 shows an RMP. Figure 6-3. Remote Monitor Panel 9315 UPS (200–300 kVA) Operation Manual S 164201036 Rev G www.powerware.com 6−3 EATON Powerware ®...
  • Page 42 Battery mode and the DC voltage is approaching its low limit. This indicator is accompanied by a horn. 6−4 EATON Powerware Number and Type of Accessories Permitted Relay Interface Module 9315 UPS (200–300 kVA) Operation Manual S 164201036 Rev G www.powerware.com ® Supervisory Contact Module...
  • Page 43: Battery Cabinets

    Several battery capacities are available. The UPS battery cabinets can be paralleled. With this capability, you can increase your battery backup time by adding battery cabinets to your UPS system. The Powerware 9315 can support up to four battery cabinets.
  • Page 44: Relay Interface Module

    Contacts are closed when approximately two minutes of battery time is remaining, before the critical load is lost. Pins 6 and 15 Contacts are closed when Utility Failure is detected. 9315 UPS (200–300 kVA) Operation Manual S 164201036 Rev G www.powerware.com ®...
  • Page 45: Figure 6-5. Supervisory Contact Module

    ON BATTERY UPS ALARM ON BYPASS SHUTDOWN IMMINENT Refer to Installing a Supervisory Contact Module" in the Powerware 9315 UPS (200–300 kVA) Installation Manual for TB2 contact configurations. 9315 UPS (200–300 kVA) Operation Manual S 164201036 Rev G www.powerware.com EATON Powerware ®...
  • Page 46 Using Features and Options This page intentionally left blank. 9315 UPS (200–300 kVA) Operation Manual S 164201036 Rev G www.powerware.com 6−8 EATON Powerware ®...
  • Page 47: Communication

    Chapter 7 Communication This chapter describes the communication features of the Powerware 9315 UPS and provides information about connecting hardware and using Terminal mode. 7.1 Locating the Communication Bays The Communication Panel inside the UPS contains a DB−9 and DB−25 serial port. The DB−9 port provides a computer interface to a Remote Monitor Panel, Relay Interface Module, or Supervisory Contact Module.
  • Page 48: Slot Cards

    Port 2 (DB−25F) RS−232 Connection (disabled by default) Figure 7-1. Location of Communication Bays on the UPS (Powerware 9315 300) 7.2 X−Slot Cards The Powerware 9315 is factory−installed with an X−Slot communication bay, and is compatible with the following cards: ConnectUPS −X Web/SNMP Card −...
  • Page 49: Lansafe Power Management Software

    LAN and telephone drops, for use with X−Slot connectivity cards, must be provided by facility planners or the customer. For installation and setup of an X−Slot card, please contact Powerware (see page 1−2). Refer to the manual supplied with the X−Slot card for user instructions.
  • Page 50: Figure 7-3. Port 1 (Db−9) Pin Assignments

    RS-232 DTR +12V NOT USED NOT USED –12V NOT USED NOT USED NOT USED NOT USED NOT USED NOT USED NOT USED Figure 7-4. Port 2 (DB−25) Pin Assignments 9315 UPS (200–300 kVA) Operation Manual S 164201036 Rev G www.powerware.com ®...
  • Page 51 Table 7-2. Pin Assignments for Port 2 (DB-25) Pin Number Pins 5 and 6 are tied together internally. NOTE 9315 UPS (200–300 kVA) Operation Manual S 164201036 Rev G www.powerware.com EATON Powerware ® Symbol Function Comments Chassis Ground Transmit Data...
  • Page 52: Configuring The Serial Ports

    Figure 7-5. Setup Serial Port 1 Screen ) appears in the upper right corner of the Setup Port screen. This button on the Monitor Panel to toggle the button. 9315 UPS (200–300 kVA) Operation Manual S 164201036 Rev G www.powerware.com ® 03 NOV 1997 14:23:45...
  • Page 53: Mode

    300 baud is not recommended for any mode except Remote Monitor. You can select a baud rate of 300, 1200, 2400, 4800, 9600, or 19200. 9315 UPS (200–300 kVA) Operation Manual S 164201036 Rev G www.powerware.com EATON Powerware ®...
  • Page 54: Data/Stop

    Each communication port on the UPS operates in one of five modes, which you select when configuring the port using the Setup Port screen. 7−8 EATON Powerware 8/1 Handshaking Disabled 9600 baud 8/1 Handshaking Disabled 9315 UPS (200–300 kVA) Operation Manual S 164201036 Rev G www.powerware.com ®...
  • Page 55: Terminal Mode

    [Ctrl]+[P] [Ctrl]+[M] [Ctrl]+[A] [Ctrl]+[B] To use a key combination, hold down the Control key and press the letter key. 9315 UPS (200–300 kVA) Operation Manual S 164201036 Rev G www.powerware.com EATON Powerware ® HH:MM:SS.hh KYWD MESSAGE Symbol...
  • Page 56: Entire Log - [Ctrl]+[P]

    Inverter Contactor (3) Closed STATUS: Bypass Contactor (K4) Open STATUS: Inverter Normal NOTICE: Room High Temperature Figure 7-6. Event History Log 9315 UPS (200–300 kVA) Operation Manual S 164201036 Rev G www.powerware.com ® 03 NOV 1997 14:23:45 0421 1000 2030 2202...
  • Page 57: Meters Printout - [Ctrl]+[M]

    The Battery area displays the DC voltage (V) and the DC current (I). Figure 7-7 shows a sample Meters printout. UPS System Normal Alarm: Notice: 9315 UPS (200–300 kVA) Operation Manual S 164201036 Rev G www.powerware.com EATON Powerware ® Uninterruptible Power System None...
  • Page 58: System Information Printout - [Ctrl]+[A]

    0.99 8 23:45 498.0 0.98 498.0 0.98 000.0 0.00 9 23:45 496.2 0.98 Figure 7-8. Battery Test Log 9315 UPS (200–300 kVA) Operation Manual S 164201036 Rev G www.powerware.com ® 15:39:31 Data 0000 0000 0000 0000 0000 0000 0000 0003...
  • Page 59: System Configuration

    If 1 is entered at the prompt, you can program the building alarm functions: Program Building Alarms 1. Enable/Disable Default Functions 2. Customize Alarm Messages 3. Return to Main Menu Enter Selection: 9315 UPS (200–300 kVA) Operation Manual S 164201036 Rev G www.powerware.com EATON Powerware ® Communication 7−13...
  • Page 60: Enable/Disable Default Functions

    The line following the Enabled Building Alarm Number(s) label indicates which building alarms are currently enabled. (In this example, Building Alarms 1 and 4 are enabled.) 7−14 EATON Powerware 9315 UPS (200–300 kVA) Operation Manual S 164201036 Rev G www.powerware.com ®...
  • Page 61: Customize Alarm Messages

    If an E is entered at the prompt, the custom messages are used for the building alarm. If a D is entered, the default messages are used for the building alarm. 9315 UPS (200–300 kVA) Operation Manual S 164201036 Rev G www.powerware.com EATON Powerware ®...
  • Page 62: Program Unit Name

    <CR> to return with no change. The password changes if the user enters and verifies the password. The entry must be six characters. 7−16 EATON Powerware 456 − 504 9315 UPS (200–300 kVA) Operation Manual S 164201036 Rev G www.powerware.com ®...
  • Page 63: Battery Test Setup

    No Battery Test Scheduled Enter <CR> to return to Battery Test Setup Menu NOTE The UPS performs only one battery test in any 24−hour period. 9315 UPS (200–300 kVA) Operation Manual S 164201036 Rev G www.powerware.com EATON Powerware ® FRI MAR 15:34 Communication 7−17...
  • Page 64: Modify Low Battery Time

    For a list of products available, contact your sales representative. 7.10 Remote Monitor Mode This mode provides the interface for the RMP, RIM, or SCM described earlier. 7−18 EATON Powerware 9315 UPS (200–300 kVA) Operation Manual S 164201036 Rev G www.powerware.com ®...
  • Page 65: Remote Notification

    Numeric paging support allows the UPS to call a paging service and send numeric messages. Housekeeping – The Housekeeping function maintains the link between the UPS and modem. 9315 UPS (200–300 kVA) Operation Manual S 164201036 Rev G www.powerware.com EATON Powerware ® Communication...
  • Page 66 Communication This page intentionally left blank. 9315 UPS (200–300 kVA) Operation Manual S 164201036 Rev G www.powerware.com 7−20 EATON Powerware ®...
  • Page 67: Important Safety Instructions

    If the battery cabinet requiring service was not provided by the UPS manufacturer, refer to the battery cabinet manufacturer’s operating manual for instructions on battery cabinet installation and maintenance, or contact your Eaton service representative. 9315 UPS (200–300 kVA) Operation Manual S 164201036 Rev G www.powerware.com EATON Powerware ®...
  • Page 68: Maintaining The Ups System 8−1

    W A R N I N G C A U T I O N A V E R T I S S E M E N T ! 9315 UPS (200–300 kVA) Operation Manual S 164201036 Rev G www.powerware.com ® buttons...
  • Page 69: Maintenance Training

    8.3 Maintenance Training A basic training course, available from Powerware, gives you a competent working knowledge of UPS operation and teaches you how to perform first level corrective maintenance. For more information about training and other services, contact the Eaton Help Desk for Powerware products (see page 1−2).
  • Page 70 Maintaining the UPS System This page intentionally left blank. 9315 UPS (200–300 kVA) Operation Manual S 164201036 Rev G www.powerware.com 8−4 EATON Powerware ®...
  • Page 71: Product Specifications

    Operating Input Current Input Current Harmonic Content Power Walk-In Power Factor Line Surges 9315 UPS (200–300 kVA) Operation Manual S 164201036 Rev G www.powerware.com EATON Powerware ® Models 225 and 300 kVA 200 and 250 kVA 225 kVA 200 kVA...
  • Page 72 Meets FCC Regulation 47, Part 15, Subpart J, for class A devices Meets IEC 801-2 specifications. Withstands up to 25 kV without damage and with no disturbance or adverse effect to the critical load. 9315 UPS (200–300 kVA) Operation Manual S 164201036 Rev G www.powerware.com ®...
  • Page 73 Float Charging Equalizing Charge Battery Charge Current Limit 9315 UPS (200–300 kVA) Operation Manual S 164201036 Rev G www.powerware.com EATON Powerware ® Sealed, maintenance-free, high rate discharge, lead-acid cells 480 Vdc (240 cells) for Powerware 9315 225 and Powerware 9315 300 420 Vdc (210 cells) for Powerware 9315 200 and Powerware 9315 250 2.25 Vdc per cell...
  • Page 74 Product Specifications This page intentionally left blank. 9315 UPS (200–300 kVA) Operation Manual S 164201036 Rev G www.powerware.com 9−4 EATON Powerware ®...
  • Page 75: Responding To System Events

    Clear Inverter AC Under Voltage Inverter Over Frequency Clear Inverter Over Frequency Inverter Under Frequency Clear Inverter Under Frequency 9315 UPS (200–300 kVA) Operation Manual S 164201036 Rev G www.powerware.com EATON Powerware ® INVERTER MESSAGES − NOTICES Bypass AC Over Voltage...
  • Page 76 Bypass Contactor (K4) Opened Input Breaker (CB1) Closed Input Breaker (CB1) Opened Inverter Contactor (K3) Closed Inverter Contactor (K3) Opened Inverter Shutdown Inverter Normal Load Transferred to Bypass Auto Mode 9315 UPS (200–300 kVA) Operation Manual S 164201036 Rev G www.powerware.com ®...
  • Page 77 Rectifier Failure Rectifier Alarm RECTIFIER MESSAGES − COMMANDS Rectifier Commanded On Rectifier Commanded Off 9315 UPS (200–300 kVA) Operation Manual S 164201036 Rev G www.powerware.com EATON Powerware ® Responding to System Events RECTIFIER MESSAGES − NOTICES Input AC Over Voltage...
  • Page 78 Clear Building Alarm 5 Building Alarm 6 Clear Building Alarm 6 Rectifier Network Down Rectifier Network Clear Inverter Network Down Inverter Network Clear Monitor Network Down Monitor Network Clear 9315 UPS (200–300 kVA) Operation Manual S 164201036 Rev G www.powerware.com ®...
  • Page 79: Using The Load Off Button

    The UPS system shuts down. Power is present inside the UPS cabinet until the upstream input feeder circuit breaker is opened. 9315 UPS (200–300 kVA) Operation Manual S 164201036 Rev G www.powerware.com EATON Powerware ® W A R N I N G W A R N I N G 11−1...
  • Page 80: Using The Load Off Button

    3. The UPS system is now reset. To restart the UPS system, follow the procedure in Chapter 4, Starting and Stopping the UPS." 11−2 EATON Powerware C A U T I O N 9315 UPS (200–300 kVA) Operation Manual S 164201036 Rev G www.powerware.com ®...
  • Page 81: Warranty

    The warrantor warrants that the Powerware three−phase UPS electronics, Eaton−built accessories, and Powerware−built battery cabinets (individually and collectively, the "Warranted Items") are free from defects in material and workmanship. If, in the opinion of Eaton, a Warranted Item is defective and the defect is within the terms of this Warranty, Eaton’s sole obligation will be to repair or replace such defective item (including by providing service, parts, and labor, as applicable), at the option of Eaton.
  • Page 82 Warranty This page intentionally left blank. 9315 UPS (200–300 kVA) Operation Manual S 164201036 Rev G www.powerware.com W−2 EATON Powerware ®...
  • Page 84 *164201036G* 164201036 G...

This manual is also suitable for:

9315